INSTALLATION GUIDE FOR

 

 

LDK SOLAR PHOTOVOLTAIC MODULES 

Version: April 2011

 

LDK SOLAR CO. LTD.

 

1

  INTRODUCTION 

 
This guide contains information regarding the installation and safe handling of 

LDK Solar 

photovoltaic 

module. All  instructions should  be  read  and  understood  before  attempting to  install. If there  are  any 
questions, please contact LDK Solar Technical Service department for further explanation. 
The following document refers to the following crystalline modules manufactured by LDK Solar: 

 
Mono-crystalline: 
 

 LDK-160D-24(s) to LDK-200D-24(s), 

LDK-200D-20(s) to LDK-250D-20(s). 

 

LDK-200D-20 to LDK-250D-20

.

 

 
Poly-crystalline : 
 

 LDK-160P-24(s)  to  LDK-200P-24(s),  LDK-200P-20(s)  to  LDK-250P-20(s)  and  LDK-250P-24(s) 

to LDK-290P-24(s). 

   LDK-200P-20 to LDK-250P-20 and LDK-250P-24 to LDK-290P-24. 

 

 
1.1 Disclaimer of liability 

 
Because  the  use  of  this  manual  and  the  conditions  or  methods  of  installation,  operation,  use  and 
maintenance of photovoltaic (PV) product are beyond LDK Solar’s control, LDK Solar does not accept 
responsibility and expressly disclaims liability for loss, damage, or expense arising out of or in any way 
connected with such installation, operation, use or maintenance. 
No  responsibility  is  assumed  by  LDK  Solar  for  any  infringement  of  patents  or  other  rights  of  third 
parties, which may result from use of the PV product. No license is granted by implication or otherwise 
under any patent or patent rights. 
The information in this manual is based on LDK Solar’s knowledge and experience and is believed to 
be reliable; but such information including product specification (without limitations) and suggestions 
do not constitute a warranty, expresses or implied. LDK Solar reserves the right to change the manual, 
the PV product, the specifications, or product information sheets without prior notice. 
 

1.2 Product identification 
 

Each module provides the following information: 
 
Nameplate: describes the product type, rated power, rated current, rated voltage, open circuit voltage, 
short  circuit  current,  all  as  measured  under  standard  test  conditions,  weight,  dimension  etc.  the 
maximum system voltage is shown on the nameplate.   
Bar code: each individual module has a unique serial number. There is only one bar code on module. It 
is permanently attached to the interior of the module visible when viewing from the front of the module. 
This bar code is inserted at the beginning of laminating. 

 

Figure 1. Example of LDK module label 

 
1.3 Quality and Safety Standards 
 

LDK Solar photovoltaic modules meet all the requirements by the following 
official Standards in terms of Quality and Safety:     
 

   IEC 61215: Design qualification and type approval 

   IEC 61730-1 and 2: Photovoltaic module safety qualification

 

 

   UL1703-2002 

   ULC/ORD-C1703-01 

   ULand Canadian Standard for safety flat-plate Photovoltaic modules and 

panels 

   ISO 9001:Quality management system for manufacture and sales of 

Photovoltaic solar modules 
 

Summary of Contents for LDK-160D-24s

Page 1: ...ed by implication or otherwise under any patent or patent rights The information in this manual is based on LDK Solar s knowledge and experience and is believed to be reliable but such information including product specification without limitations and suggestions do not constitute a warranty expresses or implied LDK Solar reserves the right to change the manual the PV product the specifications o...

Page 2: ...may generate DC voltages greater than 30 volts when exposed to direct sunlight Contact with a DC voltage of 30V or more is potentially hazardous Do not disconnect under load It is recommended to completely cover the module with an opaque material during installation to keep electricity from being generated Do not wear metallic rings watchbands ear nose lip rings or other metallic devices while ins...

Page 3: ...he Annex 1 to get more information about the use of mounting holes and load resistance of all module types Figure 3 Frame holes mounting 3 2 2 Pressure clips mounting The modules should be fixed to the structure by pressure clips on the large side or short side of the frame according to instructions on Annex 1 The clips must be mounted at the position of the mounitng hole with a 10 of total length...

Page 4: ...and properly formed personnel Check the open circuit voltage of every series module by a digital multimeter The measured values should correspond to the sum of the open circuit voltage of the individual module You will find the rated voltage in the technical specifications of the type of the module used If the measured value is significantly lower than the expected value please proceed as describe...

Page 5: ...4 LDK 250 290 P 24 s A 1580 1580 1642 1630 1642 1630 1958 1946 B 808 808 994 976 994 976 994 976 C 390 390 421 415 421 415 579 573 D 140 140 171 165 171 165 329 323 E 40 40 40 40 40 40 50 50 F 30 30 30 30 30 30 40 40 Cable 950 950 1000 1000 1000 1000 1200 1200 Weight kg 15 6 15 6 20 19 20 19 30 5 27 3 Cell type Mono 125 Multi 125 Mono 156 Mono 156 Multi 156 Multi 156 Multi 156 Multi 156 Num of Cel...

Page 6: ...ide System 1 Installation with mounting holes All module types 5400Pa Normal Installation System 2 Installation with pressure Clips A Clips System on large side B Clips System on short side All module types 5400Pa Installation according to drawing specification All module types 2400Pa Pressure clips on short side All module types Not allowed for 5400 Pa System 3 Insertion Systems A Insertion Syste...

Reviews: