LAW-CHAIN LF-318 Quick Start Manual Download Page 1

LF-318 

                                         

Freezer controller

 

 

                                                                                                                                                                                                        1030062    REV:2    C,S:758CH    070307

                                   

 

Panel 

SET

LF- 3 1 8

LAW- C H AI N

O N

O F F

Defog

Defrost

L i gh t

De

fD

ura

tio

n

Ru

nin

g

Cy

c

Te

mp

Dif

f

Te

mp

sett

ing

 

Specifications 

Supply voltage

12V/AC/50~60Hz 

Operating Temperature

-15

°

C ~ +70

°

C

 

Temperature range

-50

°

C ~ +80.0

°

C

 

Display

Seven segment LED

 

Resolution

0.1

 

Accuracy

1

 

Dimension

137*28*32mm

3

 (Panel)

 

Dimension

171*141*39mm

3

 (Box)

 

Mounting

Embedded

 

Maximum output rating (Resistive load)

Compressor 30 A/250V

Defroster 16A/250V

Defogger 8A/250V 

Light 8A/250V

Fan 8A/250V 

General parameters 

No. 

Parameter 

Description 

Range 

Default 

1. 

Temperature Setting 

The temperature to stop compressor 

-50

°

C ~ +80.0

°

-20

°

2. 

Temperature Differential 

The temperature differential to restart compressor 

+0.1

°

C ~ +15.0

°

+4.0

°

3. 

Running Cycle 

Defrosting when system running hours is over this 

setting 

0 ~ 24 hours 

4 hours 

4. 

Defrost duration 

Setting the duration of defrosting 

0 ~ 60 min. 

20 min. 

5. 

Defroster stopping temperature 

The temperature to stop defroster 

  

°

      

°

 

+25.0

°

6. 

Fan running temperature 

Fan running when temperature is higher than this 

setting 

 

°

      

°

 

0.0

°

7. 

Compressor start-up delay   

Compressor start-up delay time 

0 ~ 15 min. 

2 min. 

8. 

Sensor calibration 

Sensor calibration adjustment 

-10

°

C ~ +10.0

°

0.0

°

Protective parameters 

No.  Symbol 

Description 

Range 

Default 

1. 

LO 

Parameter protection 

y

2. 

tH 

The upper temperature limit 

tS ~ +80.0

°

+50.0

°

3. 

tL 

The lower temperature limit 

-50

°

C ~ tS 

-50

°

4. 

AH 

High temperature alarm 

tS ~ +80.0

°

+50.0

°

5. 

Ht 

Alarm when the temperature is higher than AH setting 

continuously over this duration 

0~180 min. 

90 min. 

6. 

AL 

Low temperature alarm 

-50

°

C ~ tS 

-30

°

7. 

Lt 

Alarm when the temperature is lower than AL setting 

continuously over this duration 

0~180 min. 

60 min 

8. 

FL 

Fan stops when compressor stops 

y / n 

9. 

CL 

Condenser fin cleaning interval 

0~250 days 

10. 

rt 

Display refresh latency for fraction part of temperature 

0~15 seconds 

Setting general parameters

 

 

Press and hold

SET

key for 5 seconds until “Temperature 

Setting” LED is on. Three options can be chosen at the moment 

which are

CC

(to unlock the control panel)

OO

(to lock the 

control panel) and

55

(to restore all parameters to the default 

value). Use

or

keys to select one of the options and 

press

SET

key. When

CC

is selected, no parameters can be 

modified further except parameter “Temperature Setting”. If 

you want to modify other parameters, please select

OO

 

To modify general parameters, Press

SET

key. The display will 

show symbol “888” for about 2 seconds and then “Temperature 

Setting” LED will be on. The first parameter “Temperature 

Setting” is ready to be modified. To change the parameter value, 

use

or

keys. To select next parameter, use

SET

key (each parameter and it’s related LED is listed on the right. ). 

Parameters and LEDs 

Parameters 

Temp 

setting 

LED 

(Yellow) 

Temp Diff 

LED 

(Yellow) 

Running 

Cyc 

LED 

(Green) 

Def 

Duration 

LED 

(Red) 

Temperature Setting 

On 

 

 

 

Temperature Differential 

 

On 

 

 

Running Cycle 

 

 

On   

 

Defrost Duration 

 

 

 

On 

Defroster stopping 

temperature 

Flash 

 

 

 

Fan running temperature 

 

Flash 

 

 

Compressor start-up delay 

 

 

Flash 

 

Sensor calibration 

 

 

 

Flash 

 

 

When the last parameter (Defrost Duration) is selected, press

SET

key again can leave parameter setting procedure and save all settings. If 

no any key is pressed within 30 seconds during parameter setting procedure, system will leave the parameter setting procedure and save all 

settings automatically. 