LAUREL QLS Series Quick Start Manual Download Page 7

     - 

- 7 - 

9. SPECIFICATIONS 

 

Mechanical 

Mounting ........................................................................................ 35 mm DIN rail per EN50 022 
Dimensions.................................................. 22.5 x 103 x 128 mm (0.9” x 4.1” x 5.0

) W x H x D 

Weight ....................................................................................................................... 140 g (5 oz) 
Connectors .............................................................. Detachable plug-in screw-clamp connectors 
Wire Size..........................................................................................28-12 AWG, 2.5 sq. mm max 

Signal Input 

Signal Type ........................................................4-20 mA, 1-5V, 0-5V, 0-10V (jumper selectable) 
Input Resistance ............................. 50

 for 4-20 mA, 500 k

 for 1-5V & 0-5V, 1 M

 for 0-10V 

Transmitter Excitation....................................................................... 24 Vdc nominal, 30 mA max 

Signal Outputs 

Number of Outputs ......................................................................................................................4 
Signal Type ...................................................................................................................... 4-20 mA 
Zero & Span Adjustment............................... ± 10% for each output with 25-turn potentiometers 
Signal Isolation .................................................................................. Please see graph on page 6 
Voltage Compliance ......................................................................12V (600 

 per loop at 20 mA) 

Load Regulation...................................................................... ± 0.005% of span from 0 to 600 

 

Accuracy .....................................................................................± 0.02% max span error at 23°C 
Span Tempco............................. ± 10 ppm/ºC (0.16 µA/ºC) typical, ± 25 ppm/ºC (0.4 µA/ºC) max 
AC Rejection ............................................................................................ 90 dB from DC to 60 Hz 
Response Speed ..................................... 2 ms risetime, 7 ms settling time to 0.1% of final value 
Current Test Point........................................ 10

 ± 0.5% series resistor drops 200 mV at 20 mA 

Loop Continuity Indication ........ Yellow LED lamp per loop, brightness increases with current 

Power Input 

Standard Power (QLS-1) ................. 85-264 Vac or 90-300 Vdc (DC operation not UL approved) 
Low Power Option (QLS-2) .....................................................................10-48 Vdc or 12-32 Vac 
Power Frequency .................................................................................................. DC or 47-63 Hz 
Power Isolation...................................................... 250V rms working, 2.3 kV rms per 1 min test 
Power Consumption ..........................................................3.5 W max, all loops delivering 20 mA 
Power On Indication ............................................................................................ Green LED lamp 

Environmental 

Operating Temperature ............................................................................................-40°C to 70°C 
Storage Temperature ...............................................................................................-40°C to 85°C 
Relative Humidity........................................................................... 95% at 40°C, non-condensing 
Cooling Required ....................................... Mount units with ventilation holes at top and bottom. 

Leave 6 mm (1/4") between units, or force air with a fan. 

 

Summary of Contents for QLS Series

Page 1: ...4 20 mA Current Loop Splitter Retransmitter With common mode isolation between input outputs LAUREL Electronics Inc 3183 G Airway Ave Costa Mesa CA 92626 USA Tel 714 434 6131 Fax 714 434 3766 Website...

Page 2: ...loop loose their 4 20 mA signal The transmitter voltage compliance limit may be exceeded since the voltage drops across loads in series are additive Also the 4 20 mA signal to each load device cannot...

Page 3: ...48 Vdc power connector is colored Black This unit has no power switch It will be in operation as soon as power is applied To avoid dangers of electrocution and or short circuit do not attempt to open...

Page 4: ...adjacent to the signal input connector on the circuit board The factory default input setting is 4 20 mA To change jumpers remove power then open the case by removing the screws at the four corners o...

Page 5: ...y tied to signal ground SG which can be floating or be connected to earth ground Grounded loads Any output load R can be connected to a local loop ground LG instead of current return The loop grounds...

Page 6: ...marked Z for zero and S for span on the front panel The unit is factory jumpered and calibrated so that 4 20 mA in produces 4 20 mA out on all output channels To set or calibrate an output channel app...

Page 7: ...error at 23 C Span Tempco 10 ppm C 0 16 A C typical 25 ppm C 0 4 A C max AC Rejection 90 dB from DC to 60 Hz Response Speed 2 ms risetime 7 ms settling time to 0 1 of final value Current Test Point 10...

Page 8: ...hall not apply to defects resulting from 1 Improper or inadequate maintenance by Buyer 2 Unauthorized modification or misuse 3 Operation outside the environmental specifications of the product 4 Misha...

Reviews: