- 7 -
206 Cancel
alarm
2104 Batching data reading: final gross
207 Cancel
alarm
2105 Batching data reading: alarms
209 Continue batching
1135 Totals deleting
250 Batching data reading complete
2020 Totals reading
1114 Batching data status reading
Certain data, when specifically indicated, will be written directly in the EEPROM type memory. This
memory has a limited number of writing operations (100000), therefore it is necessary to pay
particular attention to not execute useless operations on said locations. The instrument in any case
makes sure that no writing occurs if the value to be memorised is equal to the value in memory.
INSTRUMENT COMMISSIONING
Check that the display shows the weight and that when loading the load cells there is an increase in
weight. If there is not check and verify the connections and correct positioning of the load cells.
-
If the instrument has already been theoretical CALIBRATED
(plant system identification tag
present on the instrument and on the cover: load cell’s rated data already entered):
▫
reset to zero (see section
TARE WEIGHT ZERO SETTING
);
▫
check the calibration with sample weights and correct the indicated weight if necessary (see
section
REAL CALIBRATION (WITH SAMPLE WEIGHTS)
).
-
If the instrument HAS NOT BEEN CALIBRATED
(missing plant system identification tag)
proceed with calibration:
▫
if load cells data are unknown, follow the procedure in section
REAL CALIBRATION (WITH
SAMPLE WEIGHTS)
;
▫
enter the rated data of load cells following the procedure given in section
THEORETICAL
CALIBRATION
;
▫
reset to zero (see section
TARE WEIGHT ZERO SETTING
);
▫
check the calibration with sample weights and correct the indicated weight if necessary (see
section
REAL CALIBRATION (WITH SAMPLE WEIGHTS)
).
-
If you use the analog output, set the desired analog output type and the full scale value (see
section
ANALOG OUTPUT
).
BASE PROGRAM ONLY
-
If setpoint are used, set the required weight values and the relevant parameters (see sections
SETPOINT PROGRAMMING
and
OUTPUTS AND INPUTS CONFIGURATION
).
LOAD PROGRAM ONLY
Required settings for the first batching:
-
set the minimum weight value (see section
MINIMUM WEIGHT
);
-
set the
parameter (see section
OPERATION SETTINGS
);
-
set the formula 01 (see section
FORMULAS PROGRAMMING
);
-
start the batching by closing the START contact or remotely.