6
2
UNPACKING
2.1
RECEPTION AND INSPECTION
Unpack the Ultracool unit. Keep the original packaging of your unit for subsequent transportation.
Check the Ultracool unit and accessories for completeness and transport damage immediately after delivery.
In the case of any damage, external or internal, this cannot be referred to the manufacturer because all units
are checked before dispatch. If any damage is observed, this should be documented and reported to the
forwarding company. The LAUDA Ultracool S.L. warranty does not include any damages incurred during
transportation.
Accessories and consumables included as standard
Ultracool type
Designation
Quantity
Catalogue number
UC 8 to UC 100
External controller display
1
E5326071-02K
All types
Operation manual
1
- -
2.2
TRANSPORTATION
Keep the unit upright at all times. Do not tilt when shipping or moving.
The Ultracool unit must be transported by pallet jack or forklift truck.
2.3
SITE
The Ultracool unit must be installed in an atmosphere where the range of temperatures is within the indicated
margins mentioned in point 4.1. It is necessary to add ethylene glycol to the water of the circuit, as indicated
in point 4.1.
The chiller must be installed on a solid level surface that is capable of supporting a minimum of 150 kg (330
lb) for UC 2 and UC 4 models, 300 kg (660 lb) for UC 8 to UC 24 models, 650 kg (1430 lb) for UC 50
and UC 65 models and 850 kg (1875 lb) for UC 80 and UC 100 models. The floor must not have any
slope.
If the chiller has wheels, make sure to activate their brakes once the unit is in place to prevent it from
moving.
Do not place heavy objects on top of the chiller.
We recommend the installation of the Ultracool unit in a well-ventilated site and in a corrosive-free, dust-
free atmosphere.