Proline heating thermostat
75 / 123
Command
Control Parameters
Open the device parameter menu via the soft
key Menu .
With the cursor keys continue to:
Control
Control Parameters
Control Parameters
.
The adjacent window appears.
Change parameters marked with (auto) where
necessary to manual input with
Tv manual/auto
.
Select the parameters to be changed with
and confirm with .
Then in the following settings window, change
the value and confirm with .
Proven settings for control parameters and pump (Internal control)
Device type
Heat transfer liquid
Xp
_P
Tn
tn
Tv
tu
Td
td
Pump level
P 8
Water
4.0
50
35
6
4
P 8
Water
4.0
30
---
---
4
P 8
Water-Glycol
4.0
30
---
---
4
Pump Menu
End
T
set
T
fix
Control Parameters
Control para. sets
Tv manual/auto
Xp
6,0
Tn
30
Tv
(auto)
21
Td (auto)
3,5