The STARFIRE model vertical chimney, comes standard with a T-
shaped fitting and a vertical 117 cm smoke duct, all integrated into the
overall dimensions of the appliance. In the vertical smoke channel
there is a helicoidal turbine which improves the heat transfer speed
and which must be cleaned during the seasonal maintenance of the
appliance.
During installation, use a piece of
telescopic pipe to be connected to the integrated
smoke duct that allows for correct cleaning.
12. LOCATION OF THE PRODUCT
The fuel floor (parquet type) must be protected with special flame-
retardant plates (stainless steel, marble, tiles, etc.) to protect it from
radiant heat and the possible combustion of hot residues from
opening the door. Minimum distances from combustible materials
should be respected according to the requirements here indicated or
in the technical data sheet
The chimney must be at least 50 cm away from heat-
sensitive building elements or flammable materials
(wood cladding, beams or ceilings, etc.)
For proper operation, the generator must be placed
perfectly on a horizontal (level) plane.
The appliance must be installed on a floor of adequate load capacity.
If the existing construction does not meet this requirement,
appropriate measures (ex: load distribution plate) should be taken.
The installation of the appliance must ensure easy
access to the cleaning and maintenance of the
appliance itself, the exhaust ducts and the chimney.
The appliance must be installed using the anti-vibration
feet supplied as standard.
The anti-vibration mount, interposed between the chimney and the
supporting floor, significantly reduces the vibrations harmful to the
structures and annoying for people, leading to a significant reduction
in noise. We therefore advise against the permanent anchoring of the
fireplace to the floor by using cement or hardening materials, to avoid
vibrations and resonance phenomena generated by the fans mounted
on the appliance.
MINIMUM DISTANCES FROM FLAMMABLE MATERIALS:
CONSULT THE TECHNICAL DATA SHEET OF EACH MODEL
Normally these are the distances to be respected for fireplaces:
A = 29 cm (Distance from the back)
B = 34 cm (Distance from side walls)
C = 100 cm (Distance from the glass of the appliance)
D = 60 cm (a protective plate of the floor made of flammable material)
E = 12 cm (Distance from inflammable floor)
These measures can be reduced using insulating
materials. Refer to the technical data sheet of the
insulating product that you will use to comply with local
and national regulations.
Keep all flammable material like wooden furniture,
curtains, carpets and flammable fluids at least 100 cm
from the appliance when operating.
MINIMUM
DISTANCES
FROM
NON-FLAMMABLE
MATERIALS:
In the case of non-flammable materials it is
necessary to maintain a lateral and posterior distance of
at least 10 cm.
These distances are indispensable for cooling the body and for the
ordinary and extraordinary maintenance of your appliance.
13. COATING: AIR INPUT , INSPECTION AND
CANALIZATION
COATING
The coating must be self-supporting and flame-retardant (calcium-
silicate) and can not be in contact with the appliance.
The coating (non-flammable) must respect a distance:
at least 100 mm from the lateral and back of the
appliance
at least 30 mm from the front structure of the
appliance above the door
at least 5 mm from the appliance door frame.
Fireproof
plasterboard