C: Modbus
IntelliBox-I/O 2100 User Guide
174
Local Slave
The IntelliBox itself hosts a local Modbus slave role. This local slave is addressable from
Modbus/TCP at Unit Identifier 255 (0xFF).The local slave provides access to the relay
and digital I/Os as a single data block:
Address
Name
I/O
0
XIO1
User configurable as input or output
1
XIO2
User configurable as input or output
2
Relay
Output
The server treats broadcast (Unit Identifier 0) as a request to forward to the Modbus
serial port, but does not attempt to apply the function locally.
The local slave supports the following Modbus functions:
Number
Name
1
Read Coils
2
Read Discrete Inputs
3
Read Holding Registers
4
Read Input Registers
5
Write Single Coil
6
Write Single Register
15
Write Multiple Coils
16
Write Multiple Registers
23
Read/Write Multiple Registers
43/14
Read Device Identification (Basic)
Note:
Any attempt to write to an XIO that the user has configured as an input
returns exception 4 (slave device failure).