Landis+Gyr ULTRAHEAT T350 Series Operating Instructions Download Page 1

 
 

en 

Operating Instructions 

 

Ultrasonic Heating and Cooling Meter  
ULTRAHEAT

®

T350 

(2WR6…)

 

ULTRACOLD

®

T350 

(2WR6…)

 

 

26.05.2014 

Translation 

 

T350 

(2WR6…)

 

 

Gyr GmbH 

 

Subject to change without prior notice 

26.05.2014  

 

Note: These operating instructions remain with the end user following activation. 

 

Note: In the following text, the term meter refers to both 
the  heating  meter  and  the  cooling  meter,  unless other-
wise specified. 

1. 

General 

1.1 

Use 

The  T350 

(2WR6...)

  is  used  as  a  meter  for  heating  or  cooling 

consumption measurement in systems with water. 
The  meter  consists  of  two  temperature  sensors  and  an  elec-
tronic  unit  which  calculates  the  energy  consumption  from  the 
volume and temperature difference.  

 

Note:  The  meter  cannot  be  opened  without  damaging 
the security seal. 

1.2 

General notes 

The meter left the factory in a faultless condition where safety 
is  concerned.  The  manufacturer  will  provide  additional  tech-
nical  support  on  request.  Calibration  relevant  security  seal  on 
the  meter  must  not  be  damaged  or  removed.  Otherwise  the 
guarantee and calibration validity of the meter will lapse. 

 

Keep the packaging so that you can transport the meter in 
its original packaging following expiry of the calibration va-
lidity. 

 

Lay all cables at a minimum distance of 500 mm to high 
voltage and high frequency cables.  

 

A relative humidity of < 93 % at 25 °C is permissible (with-
out condensation). 

 

Avoid cavitation in the whole system due to overpressure 
i.e. at least 1 bar at qp and approx. 3 bar at qs (applies for 
approx. 80 °C). 

 

At a heating meter the mounting place of the flow sensor 
cold side is equivalent to return. The mounting place of the 
flow sensor hot side is equivalent to flow.

 

 

At a cooling meter the mounting place of the flow sensor 
hot side is equivalent to the return. The mounting place of 
the flow sensor cold side is equivalent to flow. 

2. 

Safety Information 

 

The  meters  may  only  be  used  in  building  service 
engineering  systems  and  only  for  the  applications 
described. 

 

The  local  regulations  (installation  etc.)  must  be  ad-
hered to. 

 

Adhere  to  the  operating  conditions  according  to  the 
dial  plate  during  use.  Non-adherence  can  cause 
hazards and the guarantee will lapse. 

 

Adhere to the AGFW requirements regarding circulat-
ing water (FW510). 

 

The  meter  is  only  suitable  for  circulating  water  in 
heating systems. 

 

The meter is not suitable for drinking water. 

 

Do not lift the meter by the electronic unit. 

 

Be  aware  of  sharp  edges  on  the  thread,  flange  and 
measuring tube. 

 

Only  personnel,  trained  in  the  installation  and  opera-
tion  of  meters  in  heating  and  cooling  systems,  may 
install and remove the meter. 

 

Only  install  or  remove  the  meter  when  the  pipes  are 
pressure-less. 

 

After  installing  the  meter,  check  the  leak-tightness  of 
the system. 

 

Guarantee  and  calibration  validity  will  lapse  if  the 
calibration relevant security seals are broken. 

 

Only  clean  the  meter  from  outside  with  a  soft,  lightly 
wetted cloth. Do not use any spirit or cleaning solvent. 

 

As far as disposal is concerned, the meter is a waste 
electronic  appliance  in  the  sense  of  European  Di-
rective  2002/96/EC  (WEEE)  and  it  must  not  be  dis-
posed  of  as  domestic  waste.  The  relevant  national, 
legal  regulations  must  be  observed  as  the  appliance 
must be disposed of via the channels provided for this 
purpose. The local and currently valid legislation must 
be observed. 

 

The  meter  contains  lithium  batteries.  Do  not  dispose 
of  the  meter  and  the  batteries  with  domestic  waste. 
Observe the local stipulations and laws on disposal. 

 

You  can  return  the  lithium  batteries  to  the  manufac-
turer  for  appropriate  disposal  following  use.  When 
shipping  please  observe  legal  regulations,  in  particu-
lar,  those  governing  the  labelling  and  packaging  of 
hazardous goods. 

 

Do not open the batteries. Do not bring batteries into 
contact  with  water  or  expose  to  temperatures  above 
80 °C. 

 

The  meter  does  not  have  any  lightning  protection. 
Ensure  lightning  protection  via  the  in-house  installa-
tion. 

 