1 General information

The meter has left the factory in a technically safe condition.

Further technical support is provided by the manufacturer on

request. The meter's calibration-relevant security symbols must

not be damaged or removed. Otherwise, the warranty and

calibration validity of the meter will be invalidated.

Keep the packaging in a safe place so that you can transport

the meter in its original packaging after the calibration

validity has expired.

Lay all cables at a minimum distance of 500 mm from power

and high-frequency cables.

A relative humidity of < 93 % at 25°C is permissible (non-

condensing).

Avoid overpressure cavitation throughout the system, i.e. at

least 1 bar for qp and approx. 3 bar for qs (applies for

approx. 80 °C).

The control line must not be cut, shortened or extended.

In the case of a heat meter or combined heat/cooling 

meter, the cold side installation location corresponds to the
return 

 and the warm side installation location

corresponds to the supply 

.

In the case of a cooling meter 

, the warm side

installation location corresponds to the return 

 and the

cold side installation location to the supply 

.

2 Safety instructions

Caution

The meters may only be used in building installations and

only for the applications described.

Caution

The local regulations (installation, etc.) must be observed.

Caution

The operating conditions on the nameplate must be

observed during use. Failure to comply with these

regulations can cause dangerous situations and voids all

claims arising from liability for defects as well as liability on

the basis of any expressly granted guarantees.

Caution

Comply with the requirements for circulation water (CEN /

TR 16911:2016).

Caution

The meter is only suitable for circulation water in heating

systems.

Caution

The meter is not suitable for drinking water.

Caution

Do not lift the metre on the calculator.

Caution

Pay attention to sharp edges on threads, flanges and the

measuring tube.

Caution

Only personnel trained in the installation and operation of

meters in heating/cooling systems may install and remove

the meter.

Caution

Only install or remove the meter on an unpressurised

system.

Caution

After installing the meter, check the leak tightness of the

system.

Caution

Breaking the safety marks relevant for calibration voids the

warranty and the validity of the calibration.

Caution

Avoid contact of the meter housing with silicone oils or

substances containing silicone oil.

Caution

Only clean the meter from the outside with a soft, slightly

moistened cloth. Do not use spirits or cleaning agents.

Warning

The meter must not be energised until it has been fully

assembled. Otherwise there is a risk of electric shock on

the terminals. A defective or obviously damaged device

must be disconnected from the power supply immediately

and replaced.

Warning

The meter is valid for disposal as waste electronic

equipment within the meaning of the European Directive

2012/19/EU (WEEE) and must not be disposed of as

household waste. The corresponding national and legal

regulations must be observed and the device must be

disposed of via the channels provided for this purpose. The

local and currently valid legislation must be observed.

en

Installation Instructions

Ultrasonic Heat and Cooling Meter

ULTRAHEAT T450

ULTRACOLD T450

3221101002_a

07.02.2020

Translation

T450

© Gyr

Subject to change without prior notice

07.02.2020

1

Summary of Contents for T450

Page 1: ...arantees Caution Comply with the requirements for circulation water CEN TR 16911 2016 Caution The meter is only suitable for circulation water in heating systems Caution The meter is not suitable for...

Page 2: ...ion corresponds to the return and the cold side installation location to the supply Proceed as follows to install the meter 1 Compare the installation location with the symbol on the LCD or to determi...

Page 3: ...Press button 2 briefly to complete the change The change can be checked using the symbols or on the LCD If necessary adjust the temperature sensors according to the installation requirements 4 2 Inst...

Page 4: ...e temperature sensors are horizontal or vertical Figure 7 Recommended installation position of cooling meters and combined heat cooling meters 5 Calculator The ambient temperature of the calculator mu...

Page 5: ...follows to change the battery If necessary open the battery compartment cover by loosening the screw Remove the old batteries from the battery compartment Insert the battery into the battery compartm...

Page 6: ...on Note No later than 60 seconds after installation the meter automatically detects the inserted modules and is ready for communication or pulse output 7 2 Terminal blocks 2 pin or 4 pin terminals are...

Page 7: ...be displayed without incorrect installation Error Incorrect flow direction negative Check whether the flow direction arrows on the volume meter correspond to the flow direction of the system If the di...

Page 8: ...necessary or Error in internal memory Change the device The measurements of the meter may no longer be used for legally calibrated billing Error code Error Information for Service F2 F3 F5 or F6 pers...