![Landis+Gyr Gridstream IV Series User And Installation Manual Download Page 37](http://html1.mh-extra.com/html/landis-gyr/gridstream-iv-series/gridstream-iv-series_user-and-installation-manual_673736037.webp)
Chapter 4 - Concentrator Installation
Gyr
34
98-1031 Rev AA
Series IV Concentrator U and I Guide
Figure 4 - 3. Built-out wood mounted concentrator assembly illustration, view from top
1.
Affix the mounting bracket (PN 28-1147) to the wood pole using two mounting bolts (D/A
Bolts) with washer and nut or steel bands. (Hardware parts not included in kit.)
2.
Attach the concentrator to the bracket, being aware to face the military connectors toward the
pole. Using the four (4) carriage bolts, secure it with nuts and washers included in the kit.
3.
Connect the LAN antennas to the bracket.
4.
Using the RF cables, connect the LAN antennas to the concentrator.
5.
Attach the WAN antenna to the concentrator directly.
Ground planes are built into bracket PN 28-1147. Do not install additional
ground planes to a mounting that uses this bracket.