INSTRUCTIONS FOR TROUBLE SHOOTING

LANCER ELECTRONIC ICE BANK CONTROL (EIBC)

FOR MODELS:  DELTA/1500/800

1. To check for normal PCB operation, please refer to the following instructions.

1.1

Turn power 

OFF

or ensure that power has been 

disconnected

from dispenser.

1.2

Pull PCB upward, so that it is no longer connected to the terminal block.

WARNING

TERMINAL BLOCK HAS AC LINE VOLTAGE AND SHOULD BE COVERED WITH TAPE.
INSERT A SMALL STRIP OF ELECTRICAL TAPE BETWEEN BOARD AND CONNECTOR TO
PREVENT RE-CONNECTION.
TAPE SHOULD COVER BARE ELECTRICAL CONNECTIONS TO PREVENT ELECTRICAL
SHOCK.

1.3

Disconnect both the Ice Bank probe (J2) and the Carbonator probe (J3) (if equipped) connections
from board (see Figure 1 on reverse).

1.4

Use a short copper wire, paper clip, or other means to short the Ice Bank probe terminals (J2) on
the PCB by touching all three (3) pins together.

1.5

Set Ohm test meter to measure continuity.

1.6

Reconnect power or turn dispenser ON.  Observe time and check continuity of the PCB edge 
connector (see Figure 1 on reverse).
A. The following should be observed:

1. Terminal 3 to 2 (Carbonator):  During the first 2.5 to 3.5 minutes, there should be continuity.

After 2.5 to 3.5 minutes, there should be 

NO

continuity.

2. Terminal 3 to 1 (Compressor):  During the first 4 to 6 minutes, there should be 

NO

continu-

ity.  After 4 to 6 minutes, there should be continuity.  Remove wire from J2 connector.  There
should be 

NO

continuity from 3 to 1.

3. You should be able to hear the “click” sound of the relay closing when the time delays end.

1.7

Turn electrical power

OFF

for 15 seconds and then back 

ON

again to reset Carbonator timer.  Again,

measure continuity of the PCB edge connector.
A. Terminal 3 to 2:  There should be continuity.  Use a short copper wire, paper clip, or other means

to short the Carbonator probe terminals (J3) on the PCB by touching all three (3) pins together.
This should be done before the 2.5 to 3.5 minute time limit has elapsed.  Measure the 
continuity again between Terminal 3 to 2.  There should be 

NO

continuity.

1.8

If all the above work as noted, then the board is functioning properly.  Remove tape and reconnect
board.  If any non-conformities are found, the PCB must be replaced (PN 52-0952/01).

DATE: 03/18/98
P.N.:

28-0393

6655 LANCER BLVD. • SAN ANTONIO, TEXAS 78219 USA • (210) 310-7000

FAX SALES

• USA -CANADA – 210-310-7250 • LATIN AMERICA – 210-310-7245 • ASIA – 210-310-7242 •

• EUROPE – 32-2-755-2399 • PACIFIC – 61-8-8268-1978 •

FAX ENGINEERING: • 210-310-7096

"Lancer" is the registered trademark of Lancer • Copyright — 1998 by Lancer, all rights reserved.

Reviews: