PAGE 4
Booster Pump
MASCONTROL pump controller
NO
LEVEL
Flow arrows
Electronic box
Ball valve
for system
maintenance
Follow all local codes on
pressure boost (see chart below) to arrive at total service pressure.
flucuates, use highest pressure reading and add pump's maximum
pressure boost exceeds SAFE service pressure. If city pressure
Install a PRV if incoming city pressure PLUS pump's maximum
relief valve may be added as dictated by local code.
bathrooms) a 4.6 gallon gross volume tank may be
cause pump cycling. On larger homes (3 or more
and continue to supply constant pressure and flow
(as set by the pressure reducing valve, if installed).
uses such as ice makers, glasses of water, etc.,
To prevent the pump from starting for small water
CITY BOSS provides "on demand" pump control.
Booster Pump
OPTIONAL
Valve
Pressure Reducing
city main to pump inlet
Minimum 3/4" pipe size
Pressure
Union
Check
Valve
Ball Valve
Isolating
Gauge -
Pressure
City
install a 2.0 gallon gross volume pressure tank
used. Pre-charge as described above. A pressure
until the demand is stopped. The small tank will NOT
is emptied, the MASCONTROL will start the pump
The tank will "feed" small demands. When the tank
air pre-charge to minimum 28 PSI (slightly below the
valve (if one is installed). Adjust the pressure tank
AFTER the MASCONTROL and pressure reducing
and
Pressure
OPTIONAL
Pump Controller
MASCONTROL
Total Service
Pressure Gauge-
Union
maximum in-house water pressure.
OPTIONAL Pressure Reducing Valve-
OPTIONAL Pressure Tank and Relief Valve-
Service
To
4
Mounting MASCONTROL pump controller (see Figure 1):
The MASCONTROL may be mounted directly on the booster pump's outlet.
MASCONTROL must be mounted on a vertical column with the
electronic box level, and the flow direction arrows pointing upward.
Use only Teflon tape for threaded connections.
Do not install any tap between the pump and the MASCONTROL.
Detailed system installation diagram (see Figure 2):
Relief
Valve
for system
Ball valve
maintenance
Pressure
Tank
CITY BOSS
System
Booster
Pump
MASCONTROL
Pump Controller
CITY BOSS Maximum Pressure Boost
(at 0 GPM flow)
1-SK50BOSS1
1-SK75BOSS125
1-BOSS1
1-BOSS125
1-SK50
1-SK75
39 PSI
43 PSI
Figure 2 - "CITY BOSS" Installation Diagram
City Water Pressure Booster System
Isolation Bypass Shown
Figure 1 -
=
+
Remember that incoming city pressure
plus CITY BOSS pressure boost
equals service pressure.
Note:
INSTALLATION
ATTENTION: Apply all safety rules dictated by professional standards.
WARNING: Disconnect power before installing system.
Conduit Connections:
BEFORE MOUNTING THE MASCONTROL pump controller on
the booster pump, open the MASCONTROL's electronic box
cover by removing the six screws (refer to the MASCONTROL
manual packaged with the pump controller). Press the two rubber
grommets (supplied) into the 1/2" conduit connection holes located
on the side of MASCONTROL's electronic box. A flat blade screw-
driver may be needed to help insert the grommets. "Liquid-tight"
non-metallic conduit fittings rated "NEMA 12" or "UL type 12" can
be used (not supplied) to achieve NEMA type 12 enclosure rating.
Use of metallic conduit is not recommended.
MASCONTROL 32 PSI calibrated re-start pressure);
do not exceed 20 PSI below total service pressure
Minimum incoming city pressure
REQUIRED for CITY BOSS
16 PSI
12 PSI
=
=
+
+