4. Electrical System Installation
Power requirements: a dedicated, hard-wired 115VAC/60Hz circuit with a 10 Amp (15 Amp
max) circuit breaker. Use copper conductors only. A wiring diagram is provided in the
Appendix.
Electricity is very dangerous. Wiring should be completed by a qualified
electrician. Consult the National Electric Code (NEC) and local codes for additional
requirements. In Canada, consult the Canadian Electrical Code, Part I.
4.1 Wall Thermostat (Standard)
Please follow these guidelines for thermostat installation:
•
Locate the thermostat five feet (1.5 m) above the floor on an interior wall, not in the path
of warm or cold air. Do not mount the thermostat on a cold exterior wall. Do not install
the thermostat on the heater.
•
Follow the mounting instructions that were provided with the thermostat to mount the
base.
•
Locate the provided two-wire thermostat cable with the white plug on one end.
•
Connect the black thermostat wire to the (R) Terminal by loosening screw in (R)
Terminal, inserting wire and tightening screw.
•
Connect the red thermostat wire to the (W) Terminal (Heat relay)
.
•
Reconnect the thermostat to the base. It snaps into place.
•
Connect the white plug on the burner end of the cable to the white receptacle on
the back side of the junction box on top of the heater cabinet.
Summary of Contents for MX 75
Page 2: ......
Page 41: ...8 Appendices 8 1 Wiring Diagram ...
Page 42: ......
Page 43: ...34 Call 1 888 370 6531 for Technical Support 8 2 Primary Control Instructions ...
Page 44: ...35 Call 1 888 370 6531 for Technical Support Not used with RES 75 kBTU h units ...
Page 45: ...36 Call 1 888 370 6531 for Technical Support No latch up with RES 75 kBTU h units ...
Page 46: ...37 Call 1 888 370 6531 for Technical Support ...
Page 54: ...45 Call 1 888 370 6531 for Technical Support 9 ...