background image

3

1   Important Information about the Manual

1

Important Information about the Manual

These instructions must be read carefully and completely before commencing with any work. 

The basic prerequisite for working safely is compliance with all the specified safety instruc

-

tions.

1.1

Purpose/Applicability of the Document

These instructions facilitate the safe and efficient handling of the pilot burner GFI and its

variants.
The devices correspond to the following directives and standards:
European Directives:
• 2014/30/EU (EMC Directive) (only F130I and display) 
• 2015/35/EU (Low Voltage Directive)
• (EU) 2016/426 Gas Appliance Directive (GAR)
• 2014/34/EU ATEX Directive (only devices of Ex-Zone 1 and 2)
• 2011/65/EU (RoHS2)

Harmonised European Standards:
• DIN EN 298 (only integr. flame monitoring F130I)
• DIN EN 13611 (only integr. flame monitoring F130I)
• DIN EN 61508 (only integr. flame monitoring F130I)
• IEC 60079-0 (only devices of Ex-Zone 1 and 2)
• IEC 60079-1 (only devices of Ex-Zone 1)
• IEC 60079-7 (only devices of Ex-Zone 2)
• IEC60079-15 (only devices of Ex-Zone 2)

Approvals:
• SIL3 (only integr. flame monitoring F130I)

Indien:
• Petroleum Rules, 2002 (only devices of Ex-Zone 1 and 2)

1.2

Target Group

NOTICE

All assembly, commissioning, troubleshooting and maintenance work may only be carried 

out by authorised and trained personnel. 

The device may be operated and maintained only by those who are capable of doing so 

in terms of their level of knowledge and training. 

For safety reasons, access to parameter settings must be restricted to authorised and 

trained personnel.

Summary of Contents for GFI35

Page 1: ...www lamtec de Sensors and Systems for Combustion Engineering Quick Reference for Endusers Ignition and Pilot Burner GFI35 48 70 89 and Ex Variants...

Page 2: ......

Page 3: ...l Data Pilot Burner GFI48 15 3 5 3 Technical Data Pilot Burner GFI70 17 3 5 4 Technical Data Pilot Burner GFI89 19 3 5 5 Common Technical Data for Pilot Burner GFI35 48 70 89 21 3 5 6 Special version...

Page 4: ...of Ex Zone 1 and 2 2011 65 EU RoHS2 Harmonised European Standards DIN EN 298 only integr flame monitoring F130I DIN EN 13611 only integr flame monitoring F130I DIN EN 61508 only integr flame monitori...

Page 5: ...ments in a safe place The manual is part of the product and must be kept safe and be accessible to personnel at all times In addition the following is important The manual is available when required T...

Page 6: ...ING This draws the user s attention to the possibility of imminent danger If it is not avoided it may result in death or very serious injury The plant including its surroundings could be damaged CAUTI...

Page 7: ...ed before delivery to ensure that it is working properly and safely Only use this product when it is perfect condition and in accordance with the manual the prevailing regulations and guidelines and t...

Page 8: ...age could thus occur WARNING The integrated flame scanner is not provided with a direct switch off of the fuel valves The subsequent signal processing must be carried out in the control system which i...

Page 9: ...61140 Protection against electric shock for active parts for this reason use only measurement and evaluation devices which have a double or reinforced insulation In order to provide for operating safe...

Page 10: ...ting boil ers for gas oil and solid fuels It is used for the following purposes Preheating the system Igniting the main burner Supporting the main burner flame The ignition burner is intended only for...

Page 11: ...list comprises Operating Instructions Pilot burner GFI design A B C Fig 3 1 Item list LAMTEC Pilot burner Verify correct items are accounted for and undamaged If items are missing or damaged Do not m...

Page 12: ...plate The rating plate is located on the pilot burner housing Fig 3 2 Rating plate on the LAMTEC GFI pilot burner The rating plate contains information on the configuration of the pilot burner Rating...

Page 13: ...sions A B C 1 IFM Ionisation Flame Monitoring 2 Either spark igniter or IFM GFI 48 70 89 with optional bar graph Fig 3 5 Optional GFI housing with bar graph equipment NOTICE The bar graph is optional...

Page 14: ...witching operations per day this results in a lifespan of approx 10 years Increased firing rate due to extreme operating conditions e g temperature vibration contam ination etc can significantly reduc...

Page 15: ...burner design C Fig 3 7 Dimensions of GFI35 pilot burner design C 1 Dimension outer tube length customer specific 2 Outer tube diameter 35 mm x 2 mm 1 38 x 0 078 in 5 Air supply connection 3 4 inch BS...

Page 16: ...nical Data Pilot Burner GFI48 Fig 3 8 Side view of GFI48 pilot burner design A B Fig 3 9 Dimensions of GFI48 pilot burner design A B Fig 3 10 Side view of GFI48 pilot burner Ex Zone 2 Fig 3 11 Dimensi...

Page 17: ...design C 1 Dimension outer tube length customer specific 2 Outer tube diameter 48 3 mm x 2 mm 1 90 x 0 078 in 3 Housing length versions A and B 4 Housing dimensions 5 Air supply connection 1 inch BSP...

Page 18: ...ical Data Pilot Burner GFI70 Fig 3 14 Side view of GFI70 pilot burner design A B Fig 3 15 Dimensions of GFI70 pilot burner design A B Fig 3 16 Side view of GFI70 pilot burner Ex Zone 2 Fig 3 17 Dimens...

Page 19: ...design C 1 Dimension outer tube length customer specific 2 Outer tube diameter 70 mm x 2 mm 2 75 x 0 078 in 3 Housing length versions A and B 4 Housing dimensions 5 Air supply connection 1 1 2 inch BS...

Page 20: ...ical Data Pilot Burner GFI89 Fig 3 20 Side view of GFI89 pilot burner design A B Fig 3 21 Dimensions of GFI89 pilot burner design A B Fig 3 22 Side view of GFI89 pilot burner Ex Zone 2 Fig 3 23 Dimens...

Page 21: ...ign C 1 Dimension outer tube length customer specific 2 Outer tube diameter GFI89 88 9 mm x 2 mm 3 5 x 0 078 in 3 Housing length versions A and B 4 Housing dimensions 5 Air supply connection 2 inch BS...

Page 22: ...Ignition transformer duty cycle switch on duration 16 on 1 min 10 on 50 off 20 C Ta 60 C External device fuse mandatory 4 A Integrated flame scanner SIL classification level SIL 3 Ionisation input Io...

Page 23: ...erating capacity max 43 pF m 1 kHz Rated voltage 0 8 kV 50 Hz Test voltage 2 kV Temperature range 40 80 C 40 176 F fixed installation Design B and C Power supply voltage connection to the external ign...

Page 24: ...d be shut down further operation without repair is not permitted Mode of operation Permitted mode of operation intermittent operation continuous operation Operating condition Relative humidity max 85...

Page 25: ...used for fixed installation apparatus The user shall en sure adequate clamping of the cable The cable gland size M16 is tested for low risk of mechanical danger drop height 0 4 m with 1 kg mass and s...

Page 26: ...rating pressure Min 50 mbar 0 725 psi Max 200 mbar 2 90 psi Connection GFI89 gas Gas type Natural gas or propane Flow rate gas quantity Natural gas 35 0 70 0 m3 h 45 77 91 55 yd3 h Propane 14 28 0 m3...

Page 27: ...00 kW GFI70 natural gas 500 800 kW propane 500 800 kW GFI89 natural gas I 2300 3000 kW natural gas II 4600 6000 kW propane 2300 3000 kW Connection GFI48 gas Flow rate gas quantity natural gas 25 40 m3...

Page 28: ...tube length GFI89 min 15 mbar 5 mbar 0 217 psi 0 072 psi per metre of tube length Air temperature max 80 C 176 F Relative air humidity max 70 Air quality free of dust oil grease and aerosols The qual...

Page 29: ...ata Explosion protection II 2 G Ex db IIB H2 T6 T5 GbII 2 D Ex tb IIIC T80 C T95 C Db Material copper free aluminium stainless steel 1 4404 316 Certificates Test certificates Certificate holder Rose S...

Page 30: ...Data external power unit save area Fig 3 32 External power unit safe area Fig 3 33 Dimensions external power unit safe area Technical Data Material varnished steel RAL7035 Degree of protection IP66 Te...

Page 31: ...0 C 40 248 F Pressure 1 0 bar 14 50 psi Weight NW35 1 1 kg 2 20 lb NW48 1 24 kg 2 73 lb NW70 1 5 kg 3 30 lb NW89 2 4 kg 5 29 lb Dimensions b Flange plate thickness NW35 8 mm 0 31 in NW48 10 mm 0 39 in...

Page 32: ...31 3 Product Description k Hole circle diameter NW35 100 mm 3 94 in NW48 110 mm 4 33 in NW70 130 mm 5 11 in NW89 150 mm 5 90 in DN Nominal diameter 35 48 70 89 Dimensions...

Page 33: ...outer pipe If the air block is turned 90 to the LEFT the ignition electrode is on top Connections test sockets Fig 4 1 Main components pilot burner 1 Outer tube 2 Air housing 3 Gas block 4 Connection...

Page 34: ...ilot burner is connected to the flame scanner The flame scanner measures the ionisation current and evaluates it The amount of the ionisation current can also be determined via a shunt measuring princ...

Page 35: ...ded for use in potentially explosive atmospheres recast EN 60079 0 2014 06 VDE 0170 1 2014 06 Explosive atmospheres Part 0 Equipment General requirements DANGER For ignition attempts for maintenance p...

Page 36: ...operator The following events can make the replacement of wear parts necessary Malfunctions become more frequent Device fails due to a defect Device working under adverse conditions Abnormalities duri...

Page 37: ...before removal 5 3 Customer Service Information Contact LAMTEC Service Support if you have any questions 5 4 Warranty and Delivery Terms The manufacturer s warranty conditions apply Warranty claims ar...

Page 38: ...quirements from the following regulating bodies Official Journal of the European Union L 96 309 Directive 2014 34 EU of 26 February 2014 relating to equipment and protective systems intended for use i...

Page 39: ...e the system against being restarted 6 2 Repair WARNING Safety relevant components Risk of malfunction if repaired improperly Only have repairs done by the manufacturer Do not attempt to make repairs...

Page 40: ...heat on all parts of the system and the pilot burner Risk of contact burns Allow the system and pilot burner to cool down before removal Procedure 1 Shut down the system and secure it from being switc...

Page 41: ...Disposal Notes NOTICE Improper or inadequate recycling harms the environment Observe regional disposal regulations The device itself is to be recycled as electronic waste to returned to the burner or...

Page 42: ...centring holder for the electrode rods 646R2115 Distance and centring holder with insulating piece for the electrode rods 646R2116 Flame stabilizer material 1 4301 1 4305 646R2100 Nozzle for natural g...

Page 43: ...2 material 1 4571 646R9030 Hexagonal Reducing Nipple NPT 11 4 to R 1 material 1 4571 646R9031 Conical reducer R 1 2 A X G 3 4 I MS vernickelt 646R9032 Stainless steel pressure gauge 0 160 mbar housing...

Page 44: ...for GFI 646R0100 Proposals of spare parts for a two year operation GFI35 48 70 89 Description Type Order no 1x Ionization and ignition electrode with distance and centring holder for the electrode rod...

Page 45: ...44 9 Order Information...

Page 46: ...osef Reiert Stra e 26 D 69190 Walldorf Telefon 49 0 6227 6052 0 Telefax 49 0 6227 6052 57 info lamtec de www lamtec de Druckschrift Nr DLT7130 23 EN 006 The information in this publication is subject...

Reviews: