3 Product Description
3.5.5
Common Technical Data for Pilot Burner GFI35/48/70/89
NOTICE
The electrical data are identical for all devices, only the air and gas volume flows differ.
1
The product is not permitted to be transported, stored or operated outside the specified range.
Doing so will invalidate any guarantees with regard to safety relevant functions.
2
Provide external spark quenching for inductive loads, do not connect any capacitive loads.
Design A and B: Power supply voltage connection
Electrical data
120/230 VAC (within the scope of the EU Gas Appliances
Directive), cf. rating plate Mains tolerance according to DIN
EN 60730-1
Mains frequency
50/60 Hz
Power consumption
at rated voltage = 230 V
230 VA ignition transformer, 10 VA flame scanner
at rated voltage = 120 V,
192 VA ignition transformer, 10 VA flame scanner
Ignition transformer duty cycle
switch-on duration = 16 % on 1 min. (10”on; 50” off) -
20 °C<Ta<60 °C
External device fuse (mandatory)
4 A
Integrated flame scanner
SIL-classification level
SIL 3
Ionisation input
Ionisation current
from 1 μADC flame ON
Operating mode
continuous operation capable
Flame signal output contact
Contact type
safety-oriented, floating contact
Contact type
NO, for "flame on", the contact is closed
Level of protection
SKII, base isolation for the status signal
Permissible switching voltage
1
≤ 230 VAC ≤ 48 VDC
Permissible switching current
1, 2
max. 0.5 A cos ᵠ 0.4 Min. 10 mA
Contact fusing
0.5 AT (internal, soldered)
Safety time (FFDT)
Response time in the event of the flame failure
t
V
off configurable via DIP switches to 1 s or 3 s
(standard 1 s)
Switch-on time
t
V
on ≤ 1 s
Measuring shunt
runs mains potential
Transmission ratio of measurement voltage to
ionisation current
10 mV (DC) = 1 μA (DC)
Basic error
≤ 2 %
Electrical safety
contact protection by means of protective impedances
Min. impedance of the connected
measuring device
1 MΩ