40
6
Commissioning
6.4.4
Setting Monitoring Parameters
6.4.4.1 Automatic setting
This section describes the learning processes for setting the monitoring parameters.
WARNING!
Checking the switch-off parameters
There is a risk of death and serious injury.
The preset switch-off parameters are to be verified through switch-off tests see
Section
Recording the signal with the flame ON
You must have aligned the device and set the amplification to optimum effect beforehand.
Select the firing-rate state with the lowest signal amplitude. This is normally the base fir-
ing-rate.
NOTICE
You can open the menus
Record flame ON, Record flame OFF
and
Analyse
individually
or process them as a series.
You can also have the monitoring parameters set automatically and/or set them manually.
You can switch to the next menu in the sequence or select the next step "freehand".
1. Open the
Automatic flame ON/OFF parameter setting
> Record flame ON
menu.
Fig. 6-10 "Record flame ON" display
2. Start the automatic recording of the "Flame ON" parameters by pressing
.
Fig. 6-11 The "flame ON" flame data is recorded
Summary of Contents for F300K Series
Page 2: ......
Page 26: ...25 5 User Interface 5 2 Menu tree ...
Page 31: ...30 6 Commissioning Marking information on the device Example F300K F300K UI FB30 Warning e g ...
Page 121: ...120 14 Appendix 14 3 EU Declaration of Conformity ...
Page 122: ...121 14 Appendix ...
Page 125: ...124 14 Appendix ...