13
3
Product Description
3.6
Selection Criteria
The spectral sensitivity of the flame scanners determines their suitability for specific fuels.
NOTICE
LAMTEC guarantees that the flame sensor is in perfect working order but cannot offer any
guarantees if it is used improperly.
Note the specific requirements of your plant when selecting the flame sensors. We will be
pleased to answer any questions you may have in relation to LAMTEC products.
The following table provides an overview:
*in preparation, use may only be made with LAMTEC IR fiber optic system
The suitability of the device types may differ from that indicated in the table depending on par-
ticular circumstances.
Fig. 3-5 Spectrum of the flame
Type
Fiber
Optic
Sensi
tivity
Spectral
range
in nm
Sight
angle
approx
Preferred area of application/fuels
F300K UV-4
X
++
215 ... 360
8°
•
Oil
•
Gas
•
Special gases such as refi nery gases,
blast furnace gases and hydrogen
F300K UV-4.6
X
+++
215 ... 360
10°
F300K IR-2
*
++
850 … 1200
•
Combustion chamber monitoring
F300K IR-3
*
++
1000 … 1700
60°
•
Oil-, gas-, wood-, coal- and dust-fired
furnaces with a high level of flue-gas
recirculation
•
Yellowish waste gases without UV radi-
ation or with shielding of the UV spec-
trum by water vapour and dust
F300K IR-4
*
+++
1000 ... 2200
60°
F300K UVIR-1
X
++
215 ... 360
8°
•
as F300K UV-4
•
as F300K IR-3
(double sensor)
++
1000 ... 1700
Summary of Contents for F300K IR-2
Page 2: ......
Page 26: ...25 5 User Interface 5 2 Menu tree ...
Page 31: ...30 6 Commissioning Marking information on the device Example F300K F300K UI FB30 Warning e g ...
Page 121: ...120 14 Appendix 14 3 EU Declaration of Conformity ...
Page 122: ...121 14 Appendix ...
Page 125: ...124 14 Appendix ...