background image

11

 Instructions for Maintenance

5.2.3

Checking the Flame Shut-down on Fault

WARNING!

Simulate a flame rupture or flame extinction by shunting off the fuel supply to the burner to be 
monitored by the flame scanner. Check that the signal for shutting-off the safety valve is trig-
gered off within the period of T

S

< 1 s (on safety period ’Operation’ at t

V

Off = 1 s) after extinc-

tion of the flame.

WARNING!

For the IR compact flame scanners of the F200K1(2) IR-1 and/or F200K1(2) IR-2 types, take 
into account the radiation effects characteristic of the combustion chamber. Consequently, 
switch-off tests should be carried out when the boiler has reached operating temperature. In 
particular, make sure that the sensitivity of the compact flame scanner is increased only to 
such a value required to safely and reliably monitor the flame throughout the operating range 
of the burner.

5.2.4

Fault on Flame Detection

Check this function according to chapter 

5.2.2 Preparations

 -

5.2.2.1 Checking the Compact 

Flame Scanner

.

5.2.4.1 1. Interference

Generally, interference becomes apparent by the fact that the intensity indicator of the device 
may indicate 100 %, but the green LED (’Flame in’) does not light up. Or, the green LED lights 
up for a moment, but then it does not change its intensity according to the cycle rhythm and 
goes out again. This is a cycle synchronisation fault (signal in both evaluation channel present 
at the same time). This may chiefly be due to the interference emission of the ignition trans-
former during ignition. 

Check the shielding and FPE for proper connection to the F200K

Carry out a proper grounding of the ignition transformer

Check the cables for laying and if required untangle / separate them spatially

5.2.4.2 2. Excessive Temperatures

Make sure that the maximum allowable ambient temperature of 60 °C is not exceeded at the 
installation site. In case where the temperature is expected to exceed the limit, take appropri-
ate cooling measures (e.g. cooling air enclosure FS 50, FS 51or FS 56).

Make sure that the flame scanner casing does not heat up beyond this temperature value due 
to the impact of the heat radiated by the boiler. Overheating will result in a sensitivity loss in 
the first line, or will cause damage to the sensor elements and with it may result in a total fail-
ure of the system.

’Red’ LED

lights

’Green’ LED

dark

Summary of Contents for F200K Series

Page 1: ...www lamtec de Sensors and Systems for Combustion Engineering Quick Reference for Endusers F200K Compact Flame Scanner...

Page 2: ......

Page 3: ...ioning 10 5 2 1 General Information 10 5 2 1 1 Flame Out State 10 5 2 1 2 Flame In State 10 5 2 1 3 Operating mode switchover 10 5 2 2 Preparations 11 5 2 2 1 Checking the Compact Flame Scanner 11 5 2...

Page 4: ...nts SIL 3 DIN EN ISO 9001 2008 Quality Management Systems ISO IEC 80079 34 2011 Potentially explosive areas Quality Management System QAR 2011 65 EU RoHS2 Directive UL372 Product Identification Number...

Page 5: ...dings could be damaged CAUTION This draws the user s attention to the possibility of imminent danger If it is not avoided it may result in minor injuries The plant including its surroundings could be...

Page 6: ...indrical casing comprising an axial lightinci dence aperture a processing status indicator at the rear of the unit and operational controls which can be accessed by removing the cover The device is co...

Page 7: ...please indicate separately in your order form The related stop ranges are changed in factory LAMTEC offers a version without mains frequency suppression for special applications This design requires...

Page 8: ...t angle F200K1 UV 2 and F200K2 UV 2 Ex 210 380 nm about 8 F200K1 UV 3 and F200K2 UV 3 Ex 210 380 nm about 8 F200K2 UV 6 Ex 215 360 nm about 10 F200K1 IR 2 and F200K2 IR 2 Ex 850 1200 nm about 50 F200K...

Page 9: ...n at a supply voltage 20 5 V Wire 0 5 mm2 20 AWG length 50 m 164 ft Wire 1 0 mm2 18 AWG length 100 m 328 ft Wire 2 5 mm2 14 AWG length 250 m 820 ft Deviating cable lengths p ex main criteria is the co...

Page 10: ...could be symptomatic of electromagnetic interference EMC or a de fect of the compact flame scanner refer to chapters from 5 2 4 Fault on Flame Detection to chapter 5 2 6 Faults During Operation and ch...

Page 11: ...simulated for a suffi cient period of time This is indicated by the extinction of the red LED and the pulsating light of the green LED The 6 level intensity indicator illuminates If no flame signal is...

Page 12: ...t by the fact that the intensity indicator of the device may indicate 100 but the green LED Flame in does not light up Or the green LED lights up for a moment but then it does not change its intensity...

Page 13: ...ciently be detected Check the pilot flame for stable operation 2 Interference Refer to chapter 5 2 4 Fault on Flame Detection 3 Defect in the device 5 2 6 Faults During Operation Faults occurring duri...

Page 14: ...ance 5 4 1 General Information Provisions shall be made to ensure that the light entry port of the flame sensor and the viewing port on the furnace where the sensor is fitted are regularly cleaned i e...

Page 15: ...ional Controls Fig 6 1 Monitoring and control elements F200K2 1 LED green Indication Flame in state 2 Intensity indicator for flame signal in the range 0 100 3 4 LED yellow only for F200K2 lights for...

Page 16: ...canner Testing Device FFP30 Fig 7 2 1 1 Positions of the internal jumper IR UV Fig 7 3 Dimensional drawing FFP30 A B C Threaded receptacle for F200K F300K Plug in receptacle for FFS05 FFS06 FFS07 FFS0...

Page 17: ...r supply Alkaline battery 9 V 500 mAh Automatic switch off by approx 5 min Battery life approx ca 3 years Housing Design Cylindrical aluminium housing Montage Direct connection to Threaded receptacle...

Page 18: ...Co KG Wiesenstra e 6 D 69190 Walldorf Telefon 49 0 6227 6052 0 Telefax 49 0 6227 6052 57 info lamtec de www lamtec de Print no DLT7621 19 aEN 005 The information in this publication is subject to tech...

Reviews: