5   Internal Burner Firing Rate Controller

5

Internal Burner Firing Rate Controller

5.1

Purpose

The internal firing rate controller calculates the burner firing rate against a pre-defined setpoint 

value (e.g. as a function of temperature or pressure) by comparison with the actual value. This 

position will be transferred to the electronic fuel/air ratio control as a default value.

5.2

Brief Description

The integrated firing rate controller is a PID controller with special combustion engineering 

functions. You can use it as a fixed value control or as a control by atmospheric condition. The 

following signals can be preset:
• Actual value (temperature PT 100 max 320 °C or steam pressure)
• Outside temperature or another analog signal for setpoint shift (only on control by atmos

-

pheric condition). The ETAMATIC V must be equipped with the optional hardware for con

-

trol by atmospheric condition.

• Setpoint switching (via floating contact). The burner firing rate controller releases the com

-

bustion internally.

Combustion is triggered internally by the power control unit.

5.3

Range Limits

You must set limit values in the parameters, switching the burner on and off. After a burner 

shut-down while actual temperature has not reached the switch-on threshold yet, a display will 

inform you that firing rate controller is refusing a start-up.

5.4

Moving Screen "Actual Temperature is too high"

NOTICE

The limit values should always be entered in the form of a difference from the setpoint value.

5.5

Enter Setpoint of Firing Rate Controller

Up to software version A3i1023 you can change the setpoint with parameter settings only.
From software version A3i1023 on you can change the setpoint of the firing rate controller.
This function works in case of running burner only.

- Display on firing rate rating

 Press  key 12 HAND to override this and start the ETAMATIC V, if the maximum tem

-

perature has not exceeded.

Press key 12  HAND again to switch back to automatic mode.

Press key 9 and 6 simultaneously → the setpoint in the display is blinking.

Summary of Contents for ETAMATIC V

Page 1: ...www lamtec de Sensors and Systems for Combustion Engineering Quick Reference for Endusers ETAMATIC V ETAMATIC V S...

Page 2: ......

Page 3: ...to switch the Display 12 4 8 Operation and Display of the O2 Trim 13 4 9 Calling up O2 Trim Text Messages 13 4 10 Displaying the Running Time Meter 13 4 11 Displaying Checksums and Safety Times 14 5...

Page 4: ...regulations DIN EN 298 2012 11 DIN EN 1643 2014 09 DIN EN 13611 2011 12 DIN EN 60730 2 5 2015 10 DIN EN 60730 1 2012 10 2014 35 EU Low Voltage Directive 2014 30 EU EMC Directive 2014 68 EU Pressure E...

Page 5: ...ility of imminent danger If it is not avoided it may result in death or very serious injury The plant including its surroundings could be damaged CAUTION This draws the user s attention to the possibi...

Page 6: ...es of possible actuators Combustion air valve Combustion air blower ETAMATIC VS only Fuel air valve Recirculation valve Up to 20 points usual 11 can be programmed per channel The Display is relative b...

Page 7: ...on high firing rate The integral firing rate controller is built as a PID controller with special functions for combus tion engineering You may use it as a set value controller or controlled by atmosp...

Page 8: ...ted by the 9 p Sub D plug with the ETAMATIC V Use for it the provided lead with the type no 663R0430 The data communication runs via the LAMTEC SYSTEM BUS Alternatively the possibility exists to attac...

Page 9: ...minals for burner firing rate controller and actual value on the relay module type 660R0027 The flue gas damper remains open or the flue gas fan re mains at the highest speed The external burner seque...

Page 10: ...meters Status Firing rate rating Setpoint Actual value feedback Setpoint feedback 2 Dig ital inputs Display change Compound O2 Flame inten sity UEAN Monitoring processor display 1 only if activated in...

Page 11: ...d in the parameter section only available with ETAMATIC V ETAMATIC V S the option Integrated Flame Monitor Customer Interface Using the Keys reset firing rate fault history up firing rate fault histor...

Page 12: ...output of the running time counter and the current time to de termine at which time the fault occurred Red fault LED is on Press key 17 to get STATUS display fault code Press key ENTER Plain text mess...

Page 13: ...he display hides the O2 history automatically after 5 sec O2 trim faults which last for more than 30 sec are stored They are only stored in the EEPROM once the fault is cleared up or the ETAMATIC V le...

Page 14: ...egular operation or Base firing rate operation and then returns automatically to the base setting 4 9 Calling up O2 Trim Text Messages Switch display to O2 trim 4 10 Displaying the Running Time Meter...

Page 15: ...g as soon as the burner is in operation with the relevant curve set flame signal is present 4 11 Displaying Checksums and Safety Times 1st safety time oil in seconds 2nd safety time oil in seconds 1st...

Page 16: ...ia floating contact The burner firing rate controller releases the com bustion internally Combustion is triggered internally by the power control unit 5 3 Range Limits You must set limit values in the...

Page 17: ...f the control unit reaches the shut down range the base firing rate request is emitted If the control unit s setpoint exceed the shut down range a control shut off occurs This is done by internal proc...

Page 18: ...oller 5 8 Meaning of the Display Display in FIRING RATE switch position setpoint actual value regular firing rate input internal firing rate Display in mode MANUAL regular firing rate input via channe...

Page 19: ...TE as BASIC FIRING RATE but ETA MATIC V on SETTING NA POST PURGE AU BURNER OFF no signal present EL SETTING SL CLEAR MEMORY EV SETTING PRE PURGE as PRE PURGE but ETAMATIC V on SETTING ES SETTING CONTR...

Page 20: ...ignal extinguishes during the first safety time 008 0 0 The flame signal extinguishes during the second safety time 009 0 0 Flame signal does not appear during safety time 010 0 0 Flame signal goes ou...

Page 21: ...ratio control blocked channel 4 320 1 1 Broken wire at correction input 321 1 1 Broken wire at feedback channel 1 322 1 1 Broken wire at feedback channel 2 323 1 1 Broken wire at feedback channel 3 3...

Page 22: ...g mode AU 714 0 0 Incorrect signal combination in operating mode BE 715 0 0 Incorrect signal combination in operating mode VO 716 0 0 Incorrect signal combination in operating mode ZP 717 0 0 Incorrec...

Page 23: ...o 889 0 0 Time interval between remote fault resets is too short 904 1 1 Error in reference of firing rate 911 1 1 Error in reference channel 1 912 1 1 Error in reference channel 2 913 1 1 Error in re...

Page 24: ...23 6 Appendix 6 3 Calling Up the Condition of the Digital Inputs Meaning of the digital inputs of the ETAMATIC V Switch to digital inputs with keys 16 and 17 Signal applies Signal does not apply...

Page 25: ...according to IEC 60127 2 Sheet 5 1500A 250VAC Melting Integral I t 40 A s e g Littelfuse 0215002 M XP Fuses that fulfill these requirements are ceramic tube fuses with the marking T2AH 250V Fig 6 3 B...

Page 26: ...25 6 Appendix 6 5 EU Declaration of Conformity...

Page 27: ...26 6 Appendix...

Page 28: ...27 6 Appendix...

Page 29: ...28 6 Appendix...

Page 30: ...KG Wiesenstra e 6 D 69190 Walldorf Telefon 49 0 6227 6052 0 Telefax 49 0 6227 6052 57 info lamtec de www lamtec de Publication no DLT2004 20 aEN 022 The information in this publication is subject to t...

Reviews: