Parameter 0050 and 0051 are necessary only in case a setpoint changeover is required.
8.1.5
Setpoint Changeover
You can switch setpoint via input at terminal 5. When you use a version with fixed setpoint val-
ue you are able to select through this contact one of two values listed in parameters P0048
and P0050 with this contact.
While control by atmospheric conditions is activated additionally you are able to select be-
tween two pairs of limit values (see control by atmospheric conditions and limit ranges). Pa-
rameters for setpoint 1 (for setpoint switching) and setpoint min 1 (for control by atmospheric
conditions) are the same. Similarly, parameters setpoint 2 and setpoint min 2. The corre-
sponding content is assigned accordingly to selected configuration.
While ’control by atmospheric conditions’ is activated and parameters are set correspondingly
you may also implement an external setpoint default. This means setpoint values can be ad-
justed via potentiometer (or switched through resistors) manually or automatically. By con-
necting a change-over switch, you can implement a night-time reduction instead of ’control by
atmospheric conditions’. A ’control by atmospheric conditions’ in combination with night-time
reduction is also possible. In order to achieve this combine the control by atmospheric condi-
tions with setpoint switch over.
8.1.6
Start-up Sequence
The firing rate controller has a start-up cycle in order to slow down burners’ firing rate while
starting. The start-up cycle is passed during each new burner start. The internal firing rate is
held at user-adjusted value (P 0044) as long as the boiler is cold. The actual value is below
parameter set limit (P 0043. If controllers’ actual value is larger/equal to the parameter set
start-up maximum temperature, this startup cycle is cancelled.
In order to prevent that too large power demand of the plant having the consequence that boil-
er temperature for ending start-up cycle is not reached, in parallel a startup timer is also trig-
gered in parallel (timer adjustable by operator, P0045). As internal firing rate reaches
parameter set start-up firing rate, output is increased linearly step-by-step up to maximum
firing rate. The rise of this linear increase is calculated from parameter set start-up time.
When the start-up circuit is active, the icon
is displayed in the UI300.
0052
0; in the usage of 0 ... 20 mA at the setpoint input
0052
40; in the usage of 4 ... 20 mA at the setpoint input
0053
200
0048
Setpoint 1 which should be set with 0/4 mA at setpoint input
0049
Setpoint 1 which should be set with 20 mA at setpoint input
0050
Setpoint 2 which should be set with 0/4 mA at setpoint input
0051
Setpoint 2 which should be set with 20 mA at setpoint input
Summary of Contents for BT300 BurnerTronic
Page 2: ......
Page 25: ...24 3 Product Description Fig 3 9 Temperature derating BT300 for operation 2000 m NHN...
Page 49: ...48 4 Design and Functions Fig 4 20 Oil with pilot burner BT300...
Page 50: ...49 4 Design and Functions Fig 4 21 Oil without pilot burner BT300...
Page 51: ...50 4 Design and Functions Fig 4 22 Gas with pilot burner and leakage test BT300...
Page 52: ...51 4 Design and Functions Fig 4 23 Gas without pilot burner and leakage test BT300...
Page 53: ...52 4 Design and Functions Fig 4 24 Oil without pilot burner BT335...
Page 54: ...53 4 Design and Functions Fig 4 25 Gas without pilot burner and leakage test BT335...
Page 59: ...58 4 Design and Functions Fig 4 28 Leakage test process diagram...
Page 98: ...97 6 Operating Control and Displays...
Page 99: ...98 6 Operating Control and Displays...
Page 103: ...102 6 Operating Control and Displays...
Page 105: ...104 6 Operating Control and Displays...
Page 106: ...105 6 Operating Control and Displays...
Page 107: ...106 6 Operating Control and Displays...
Page 109: ...108 6 Operating Control and Displays...
Page 126: ...125 6 Operating Control and Displays 6 3 4 2 Curve Table Fig 6 37 Curve table window...
Page 246: ...242 10 EU Declaration of Conformity 10 EU Declaration of Conformity...
Page 247: ...243 10 EU Declaration of Conformity...