cod. 3541T620 - Rev. 05 - 04/2022
144
EN
DORA
90 LT - 120 LT
Parame-
ters
Description
Range
Default
Notes
P55
Band 1 evaporator temperature proportional
regulation
1÷20°C
4°C
Modifiable
P56
Differential temperature with activation of max-
imum speed
P57÷20°C
2°C
Modifiable
P57
Differential temperature with deactivation of
maximum speed
1°C÷P56
1°C
Modifiable
P58
Use of the evaporator fan with the compressor
off
0 = OFF
1 = ON with manual speed
control
2 = ON with automatic speed
control
0
Modifiable
P59
Evaporator fan speed (EC) with compressor off 0÷100%
40%
Modifiable
P60
Temperature difference 1 of evaporation of the
air for the calculation of the setpoint
1÷25°C
4°C
Modifiable
P61
Temperature difference 2 of evaporation of the
air for the calculation of the setpoint
1÷25°C
2°C
Modifiable
P62
Temperature difference 3 of evaporation of the
air for the calculation of the setpoint
1÷25°C
6°C
Modifiable
P63
Temperature difference 4 of evaporation of the
air for the calculation of the setpoint
1÷25°C
3°C
Modifiable
P64
Temperature difference 5 of evaporation of the
air for the calculation of the setpoint
1÷25°C
10°C
Modifiable
P65
Temperature difference 6 of evaporation of the
air for the calculation of the setpoint
1÷25°C
18°C
Modifiable
P66
Band 2 evaporator temperature proportional
regulation
1÷20°C
2°C
Modifiable
P67
Band 3 evaporator temperature proportional
regulation
1÷20°C
9°C
Modifiable
P68
Band 4 evaporator temperature proportional
regulation
1÷20°C
5°C
Modifiable
P69
Band 5 evaporator temperature proportional
regulation
1÷20°C
10°C
Modifiable
P70
Band 6 evaporator temperature proportional
regulation
1÷20°C
5°C
Modifiable
P71
EC evaporator fan speed reduction for silent
mode
0÷40%
15%
Modifiable
P72
EC fan speed regulator gain
1÷100
5
Modifiable
(1) = NOT USABLE FOR THIS EQUIPMENT