background image

"

"

"

"

Input Voltage selective by Terminal Block position

*Note: Input current ratings given are maximum when output Repetition Rate is =>10Hz. Consult
Factory if model used at less than 10Hz.

--

--

--

7A

--

30A

20A

10A

90-140

50/60Hz

100-120

50/60Hz

13.5

10A

6.6A

3.5A

--

14.5A

10A

5A

180-240

50/60Hz

200-220

50/60Hz

202A

152A

102A

500A

202A

152A

102A

500A

Design

Range

Nameplate

Range

Current (PFC)

Non PFC

Current (No PFC)

Input Voltage (VAC)

Table 2.2 Input Voltage Chart

#

#

#

#

  

  

  

  

0.98

0.65

All models

PFC

Non PFC

Table 2.3: Power Factor

 

Better than 85%

  

 

 

  

Less than 0.3 Joules all models

 

0.2% per hour after 1 hour warm-up.

  

 

 

  

 

±0.2% to 300 Hz. For higher repetition rates, consult factory

 

  

 

 

 

100ppm per °C

 

 

Storage -40 to +85°C. Operating -20 to +45°C

83-493-001 Revision G

2 - 2

Specifications

Summary of Contents for pmn

Page 1: ...405 ESSEX ROAD NEPTUNE NJ 07753 TEL 732 922 9300 FAX 732 922 9334 INSTRUCTION MANUAL FOR 83 493 001 Revision G MODEL SERIAL NUMBER...

Page 2: ...23 2 Suffix RFI 2 3 2 23 1 Suffix SYS 2 3 2 23 Options 2 3 2 22 Accessories 2 3 2 21 Note for PFC Units 2 3 2 20 ESD 2 3 2 19 Transient Line Protection 2 3 2 18 Agency Approvals 2 3 2 17 Protection 2...

Page 3: ...Bias Measurements 5 1 Figure 5 2 Output Current Measurement 5 1 Figure 5 1 Output Voltage Waveform 4 2 Figure 4 1 Eample Of Interface Connection 3 4 Figure 3 3 Output Ground Connection 3 2 Figure 3 2...

Page 4: ...er A high performance control module precisely regulates the output voltage automatically compensating for line load temperature rep rate variations Normal external fault conditions such as line dropo...

Page 5: ...kV 40kV All models continuously variable from 0 to 100 of rated output voltage 2 4 1 LINEARITY Linear to within 1 of full scale 2 4 2 ACCURACY 1 of rated Available as fixed Positive or Negative Insula...

Page 6: ...50 60Hz 200 220 50 60Hz 202A 152A 102A 500A 202A 152A 102A 500A Design Range Nameplate Range Current PFC Non PFC Current No PFC Input Voltage VAC Table 2 2 Input Voltage Chart 0 98 0 65 All models PF...

Page 7: ...e Inhibit Line the power supply will reach normal operation mode and therefore all other published specifications within 50 ms Detachable 8 feet 2 4 meters HV Cable see Table 2 1 15 pin D plug mating...

Page 8: ...110 100 to 120 VAC input option for non power factor corrected 152A 1500 J s model NOTE 152A power supply with suffix 110 at 100 120VAC must be operated with internal 20A fuses F1 F2 on inverter bd re...

Page 9: ...Figure 2 1 Mechanical Dimensions for 500A 102A 152A Outputs up to 6KV for grounding instructions see SECTION 3 6 83 493 001 Revision G 2 5 Specifications...

Page 10: ...Figure 2 2 Mechanical Dimensions for 500A 102A 152A Outputs from 7KV to 40KV for grounding instructions see SECTION 3 6 83 493 001 Revision G 2 6 Specifications...

Page 11: ...Figure 2 3 Mechanical Dimensions for 202A Outputs up to 6KV for grounding instructions see SECTION 3 6 83 493 001 Revision G 2 7 Specifications...

Page 12: ...Figure 2 4 Mechanical Dimensions for 202A Outputs from 7KV to 40KV for grounding instructions see SECTION 3 6 83 493 001 Revision G 2 8 Specifications...

Page 13: ...hes 101 6mm to minimize stress on the insulation Generally at least 4 inches 101 6mm of clearance should be allowed at the inlet of the power supply and 2 inches 50 8mm at the sides When operating in...

Page 14: ...fuses F1 and F2 on the Inverter Board replaced by copper bus provided with the supply Use external 30A UL VDC Approved Fuse Circuit Breaker NOTE For Application At less than 10 Hz Please see section 5...

Page 15: ...educes long term corona effects Keep the minimum HV cable bend radius greater than 4 inches 101 6mm to minimize stress on the insulation Keep the HV cable as distant as possible from the input power a...

Page 16: ...the supply to the load as shown in Figure 3 3 See Figure 2 1 and 2 2 for grounding cable configuration Figure 3 3 Output Ground Connection 3 6 3 FOR UNITS WITH O P VOLTAGE 6kV The ground connection is...

Page 17: ...cuit return Also chassis earth ground OUTPUT GND 14 15V regulated Can be used for user programming applications 20mA max OUTPUT 15V 9 11 A 10 to 15V with respect to ground disables the unit Open or gr...

Page 18: ...Figure 4 1 Eample Of Interface Connection 83 493 001 Revision G 4 2 Operations...

Page 19: ...protection mode and indicate a LOAD FAULT An overload condition can occur if the INHIBIT signal is missing allowing HV switch to latch up It can also occur if the discharge rep rate is too high to all...

Page 20: ...roducing an average of 100 J sec The following formulas can be used to determine the average and peak charge rate Peak Charge Rate C OUTPUT LOAD CAPACITOR 1 2 CV2 TC V PROGRAMMED OUTPUT VOLTAGE Averag...

Page 21: ...ach of the power supplies operate at the same time with the total charge rate equal to the sum of each Sometimes when operating several units in parallel the high total power generates noise which int...

Page 22: ...where VO is the High Voltage being measured VM R2 R1R2 VO Making a pulsed measurement with an oscilloscope requires a compensated HV probe having a wide bandwidth Simply connecting a DC probe through...

Page 23: ...age power must be used to determine line current See Section 5 7 The 500A 102A 152A 202A supplies can be used as a constant voltage supply by the addition of an external filter capacitor The value of...

Page 24: ...apacitors can average the power drawn from the power factor correcting circuit At lower pulse rates the output stage will attempt to draw twice the rated average power fro the PFC circuit The internal...

Page 25: ...ould be limited to less than five minutes No maintenance is required under normal operating conditions Occasional vacuum or blow out of the chassis may be required when operated in extremely dirty env...

Reviews: