Procedure for Changing /removing the alarm CL on the LAE AT1-5 

Controller 

 
 
 
The front panel of the LAE RL2 Controller has an LED display and four push-
buttons which will be referred to in numerical order 1-4 from left to right. The LED 
Display normally shows the measured temperature. 

 
 

 

 
 
 

In order to remove the alarm CL (CONDENSER CLEAN) , it is now necessary to 
operate these push-buttons in certain combinations as outlined below. The 
following points correspond in number with the diagrams on the following page. 

 

1.  Press and hold buttons 1 and 4 simultaneously. 
2. 

After 5 seconds, the LED display shows ‘ScL’ – release buttons 1 and 4. 

3.  Press button 3 until the display shows ACC  
4.  Display will now reads ACC 
5.  Press and hold button 1 
6.  Immediately the LED display shows the current setting (25) 
7.  While still holding button 1, repeatedly press button 3 to increase the 

setting 

8.  While still holding button 1, repeatedly press button 2 to decrease the 

setting (advised to take this to zero to deactivate the alarm) 

 