background image

We thank you for choosing an LAE electronic product. Before proceeding to the installation of this unit, please read this
instructions sheet carefully; only in this way you will obtain maximum performances and safety.

1. INSTALLATION

1.1

LTS12 has got a size of 77x35x77 mm (WxHxD), it must be inserted into the panel through a 71x29 mm hole and

secured via the suitable brackets exerting correct strength. The rubber gasket must be placed between the panel and the
instrument front, so please make sure that there are no gaps allowing liquid infiltrations.

1.2 

The unit works with an ambient temperature between -10°.. +50°C and 15%.. 80% relative humidity. To reduce the

effects of electro-magnetic interference, place the probe cable and the unit itself as away as possible from power lines.

1.3

Probe and power supply must be connected strictly following the diagram appearing on the enclosure. If present, the

probe screen must be earthed, by connecting it to the metal frame. If needed, the unit must be powered by means of the
suitable transformer mod. TRxxx.

Where delicate or valuable products have to be maintained under strict conditions, please use a separate controller for limit
and alarm functions.

2. CONFIGURATION (SETUP)

Thanks to the configuration parameters, the LTS12 can suit scale, resolution and sensor type. Access to the configuration
takes place through the following sequence: switch off the unit, keep buttons  +

pressed, then switch on unit again. Scroll

through the parameter list with 

or 

until you get to the desired one, then get its value displayed with 

and change it

with +

or . 

Exit from the SETUP takes place by letting the keypad untouched for 10 seconds.

Parameter 

SCL

provides the readout scale, i.e.: with SCL=01 there is no modification of the measured value, while with

SCL=02, there is a scale conversion from °C to °F (to be used for temperature measurements only). In this latter case, 0.1
resolution is not available.
With SCL=01 resolution is based upon the value set to 

ACC

; with ACC=01 or 02 resolution is set to respectively 1 or 0.1.

With ACC=03 you will obtain the maximum resolution allowed by the display, i.e.: 0.1 for values between –19.9 and 99.9
and  1 outside of these limits.
Through 

SIM

it’s possible to simulate different sensor response times to changes of the value measured, therefore: by setting

SIM to values greater than 0, the resulting effect will be a proportional reduction of the displayed data change.
If the model you own accepts two types of input, then select the one you want to use by means of parameter 

TYP

following

the table here below:

SCL

Readout scale 

01=normal, 02=°F  

ACC

Resolution 

01=1;  02=0.1;  03=autorange  

TYP

Type of sensor 

0; 1   

LOR

Minimum range limit 

-199 .. 999  

HOR

Maximum range limit 

-199 .. 999  

SIM

Display indication slowdown 

0 .. 100  

LAD

Zero calibration 

--  

HAD

Span calibration

--

M

ODEL

TYP=0

TYP=1

LTS12 PT 

Pt100 DIN43760 

PTC KTY81-121  

LTS12 TC

T/C “J” Fe-CuNi 

T/C “K” NiCr-Ni  

LTS12 AV

----- 0... 

1V

INSTRUCTIONS FOR INSTALLATION AND USE.

LTS12

Reviews: