BA_078_en_10.01 Level transmitter PASCAL Ci4 LEVEL
Page 29/36
6.5.5.2
“Display mode” submenue
In the "Display mode" submenue, you configure the representation of the measured values
and additional information on the display.
With the menue item “Screen layout” you configure the information that is displayed and its
layout. Up to five values can be displayed at the same time. In the additional menue en-
tries "1st value" to "5th value" you define the contents of the placeholders in the layout.
The various layouts as well as the possible content of the values are described in Chapter
6.3.4.
6.5.6
"Measurement/output" menue
In the "Measurement/output" menue, you configure the damping and measuring rate. In
addition you select and parameterise the measurand to be shown at the current output.
Menue entry
Description
Damping
Setting the damping of the output signal
Measuring rate
Setting the measuring rate (20 or 100 Hz)
Select output value
Select value that shall be shown at the current output (height,
volumen, weight or pressure)
Value at 4 mA
Value of the selected measurand that should correspond to 4 mA
(lower range value)
Value at 20 mA
Value of the selected measurand that should correspond to 20
mA (upper range value)
Alarm current
Selection of the alarm current: High (>21 mA) or low (<3.6 mA)
Lower current limit
Limit of the lower output current (3.8…4.0 mA)
Upper current limit
Limit of the upper output current (20…21 mA)
Table 21: “Measurement/Output” menue
Independent from the setting of the upper and lower current limit, the set measuring range
always corresponds to a current range of 4…20 mA.