41
Service Manual - NeoTherm 500
Yes
Blower goes
to full speed?
Unplug J2. This is the
control signal to the blower.
No
Yes
Check wiring
harness. Wires
OK?
No
Replace wire harness
No
Has call for heat?
At start of test, unit should be ready to run (”Standby”)
Blower runs
Problem with temp. sensor(s)
Short contacts
for call for heat:
CH: TB7 5-6
DHW: TB6 5-6
Blower does not run
Bad blower. Replace the blower.
B22
Checking the Blower