Mascot LX Service Manual
Intake vent
or exhaust flue
blocked?
Yes
No
Clear the vent and flue.
Check the bird screens
or terminals.
Check for blocked air intake
and exhaust vents.
Remove the blower and
check it. See the instructions
in this section.
.
Mechanical problem
with blower?
Yes
No
Test the air pressure switch.
Switch
is OK?
No
Yes
Want continuity when blower is off
Heat exchanger
is plugged?
Yes
Air Pressure Switch
B12