Mascot II Boilers and Water Heaters
Page 17
6.5 Recognized Chemicals
The following manufacturers offer glycols,
inhibitors, and anti-foamants that are suitable for use
in the Mascot II. Please refer to the manufacturers
instructions for proper selection and application.
1. Sentinel Performance Solutions Group
2. Hercules Chemical Company
3. Dow Chemical Company
6.6 Hot Water Piping
6.6.1 Domestic Hot Water Piping (LMC)
Connect domestic hot and cold water piping to the
boiler at locations noted in
Figure 13
. Expected DHW
performance is indicated in
Table 8
.
Use of flow restrictor is optional to prevent colder
water at excessive flow rates. Contact Laars for alternate
configurations.
6.6.2 Indirect Water Heater Piping (LMH)
The LMH model can control an indirect water
heater zone. Pipe to the locations shown in
Figure 13
.
Zone valve and associated wiring are not required.
Setpoint is made via aquastat located on the indirect
water heater, or can be controlled at the boiler via a
remote sensor.
6.7 Condensate Drain
A condensate drain trap is built into the Mascot II.
Connect a 3/4” PVC pipe between the drain
connection and a floor drain (or a condensate pump if a
floor drain is not accessible).
The condensate drain must be installed so
as to prevent accumulation of condensate. When
a condensate pump is not used, the tubing must
continuously slope downward toward the drain with no
spiraling.
Consult local codes for the disposal method.
Caution
Condensate is mildly acidic (pH=5), and may harm
some floor drains and/or pipes, particularly those
that are metal. Ensure that the drain, drainpipe,
and anything that will come in contact with the
condensate can withstand the acidity, or neutralize
the condensate before disposal.
Damage caused by
failure to install a neutralizer kit or to adequately
treat condensate will not be the manufacturer’s
responsibility.
Figure 14. Hydronic Piping — Low temp system with indirect water heater (LMH using internal 3-way).
Summary of Contents for LMH
Page 42: ...LAARS Heating Systems Page 40 Figure 28 Panel Assembly Door Top...
Page 43: ...Mascot II Boilers and Water Heaters Page 41 Figure 29 Panel Assembly Door Middle...
Page 44: ...LAARS Heating Systems Page 42 Figure 30 Panel Assembly Door Bottom...
Page 45: ...Mascot II Boilers and Water Heaters Page 43 Figure 31 Base Jacket Assembly...
Page 46: ...LAARS Heating Systems Page 44 Figure 32 Heat Exchanger Cabinet Fan...
Page 47: ...Mascot II Boilers and Water Heaters Page 45 Figure 33 Heat Exchanger Burner Components...
Page 48: ...LAARS Heating Systems Page 46 Figure 34 Pump Assembly Components...
Page 49: ...Mascot II Boilers and Water Heaters Page 47 Figure 35 Plumbing Components...
Page 50: ...LAARS Heating Systems Page 48...