ESCR 

Quick Start Guide

La Marche ESCR Engine Starting Battery Charger: 

Getting started

La Marche Mfg. (A U.S. Company)

106 Bradrock Drive, Des Plaines, IL 60018

Tel: 847.299.1188   Fax: 847.299.3061

[email protected]

www.lamarchemfg.com

WARNING: Please read the Important Safety Instructions before proceeding. 

1

Remove Bottom Panel

Make Sure to check for any shipping damages before getting started. 

1

2

Connect AC 120/208-240. Te 
unit automatically detects the 
AC input without changing any 
taps or switches. Battery does 
not need to be connected 
during configuration mode. 

3

To change setting, you must enter the 
configuration mode by pressing the 
CONFIG/OK red button located on the 
front panel. The unit does not supply 
output in the configuration mode.

Units are factory set at 12 Volt. 

Reset Button

OK Button

Cell Type
       6 Lead Acid 
Float Voltage
        2.25 Volts per Cell
Equalize Voltage
        2.33 Volts per Cell
Equalize Timer
        8hr - Equalize Timer
        Manual - Equalize Cycle
Current Limit
        105%
Temperature Compensation
        Disabled 
Alarm Setting
        Alarm Delay - 5 Sec
        Low VDC - 1.98 VDC
        High VDC - 2.45 VDC
Low DC Current - 0.5 Amps
        AC Failure 

.

.
.

.

.

.
.

.

ESCR-40/20-12/24V-AV1:

ESCR-20/10-12/24V-AV1