3
1
Installing the A77
1.1
Mounting the A77
When mounting the A77 in ANY configuration, consider the size and weight of the charger. The wall, rack,
and/or floor must be able to support the weight of the charger as well as an additional safety factor. Verify the
weight of the A77 charger using Appendix A or Appendix B, and the method of mounting using Table 1 below.
The location chosen for the charger should be within an ambient temperature range of 32 to 122
˚
F (0 to 50
˚
C)
with a non-condensing relative humidity no higher than 95%. The A77 should be mounted in an area free of
explosive materials and away from drips and splatter. The A77 utilizes convection cooling so a clearance of at
least 6in (152mm) of free air must be maintained on the top, bottom and both sides for cooling air. Maintain
36in (914mm) or more of clearance at the front of the charger in order to allow for operation and maintenance.
Enclosure
Number
Cable Entry
Standard
Mounting
Optional
Mounting Kits
AC Input
DC Output
10
Right Top/Bottom
Left Top/Bottom
Wall
19"/23" Rack
Mount
or Floor Mount
477
Right Top/Bottom
Left Top/Bottom
Wall
977
Right Top/Bottom
Left Top/Bottom
Floor
23" Rack Mount
72
N
Top/Bottom Top/Bottom
Floor
Floor-Mount Only
46N
Top/Bottom Top/Bottom
Floor
Floor-Mount Only
47N
Top/Bottom Top/Bottom
Floor
Floor-Mount Only
57
Top/Bottom Top/Bottom
Floor
Floor-Mount Only
Table 1 - Available mounting methods for each of the A77 enclosure sizes
NOTE: The 72N, 46N, 47N and 57 enclosures are floor mount only. These enclosures CANNOT be rack or wall-
mounted.