background image

 

 

 

INSTALLATION MANUAL 

FOR THE 

 
 

 

OF 

SOLAR PHOTOVOLTAIC POWER MODULES 

Please read this manual carefully before installing the modules. 

KYOCERA 

                               6C-207463

 

 

1. INTRODUCTION 

As the  world leader in the  development and application of 
high  technology  ceramic/silica  materials,  Kyocera  offers  a 
wide range of highly efficient and reliable crystalline silicon 
solar photovoltaic (PV) power modules. Kyocera began to 
extensively  research  PV  technology  in  1975  and 
commenced manufacturing operations in 1978.  Since then, 
Kyocera  has  supplied  millions  of  cells  and  modules 
throughout  the  world.  With  years  of  experience  and 
state-of-the-art  technology,  Kyocera  provides  the  highest 
quality PV power modules in a range of sizes designed to 
meet the requirements of the most demanding energy and 
power users worldwide. 

 

2. APPLICATIONS 

KDxxxGX-LPU  series  modules  are  a  reliable,  virtually 
maintenance-free  direct  current  (DC)  power  source, 
designed to operate at the highest level of efficiency.  
KDxxxGX-LPU  series  modules  are  ideal  for  remote 
home,  water  pumping,  utility-tied,  telecommunications 
and many other applications either with or without using 
storage batteries.  

 

3. WARNINGS & SAFETY

 

PV modules generate electricity when exposed to light. 
Arrays  of  many  modules  can  cause  lethal  shock  and 
burn  hazards.  Only  authorized  and  trained  personnel 
should have access to these modules. To reduce the risk 
of  electrical  shock  or  burns,  modules  may  be  covered 
with an opaque material during installation. Do not touch 
live  terminals  with  bare  hands.  Use  insulated  tools  for 
electrical  connections.  Do  not  use  these  modules  for 
solar concentration. 

 

 

PERMIT 

・ 

Before  installing  your  PV  system,  contact  local 
authorities  to  determine  the  necessary  permits, 
installation and inspection requirements.

 

 

INSTALLATION AND OPERATION 

・ 

Systems should be installed by qualified personnel only. 
The system involves electricity, and can be dangerous if 
the personnel are not familiar with the appropriate safety 
procedures. 

・ 

Do not step on the module. 

・ 

Although 

KDxxxGX-LPU

  series  modules  are  quite 

durable, the glass can be broken (and the module will no 
longer  work  properly)  if  it  is  dropped  or  hit  by  tools  or 
other objects. 

・ 

The module frame is made of anodized aluminum, and 
therefore corrosion can occur if the module is subject to 
a salt-water environment and is in contact with another 
type of metal (electrolytic corrosion). If required, PVC or 
stainless  steel  washers  can  be  placed  between  PV 
module frame and support structure to prevent this type 
of corrosion. 

・ 

KDxxxGX-LPU

  series  module  frame(s)  must  be 

attached  to  a  support  structure  by  one  of  the  methods 
described in Section 6, Installing 

KDxxxGX-LPU

 series 

module(s).

 

・ 

Module  support  structures  to  be  used  to  support 

KDxxxGX-LPU

 series module(s) should be  wind rated 

and approved   by the appropriate local and civil codes 
prior to installation.

 

・ 

Do not expose the back of the module to direct sunlight

 

・ 

In Canada installation shall be in accordance with CSA 
C22.1,  Safety  Standard  for  Electrical  Installations, 
Canadian Electrical Code, Part 1. 

 

FIRE RATING 

・ 

In case of roof installation, PV module assembly shall be 
mounted  on  a  fire  resistant  roof  covering  rated  for  the 
application. 

KDxxxGX-LPU

  series  modules  are 

comprised  of  a  glass  front  surface,  polyethylene 
terephthalate (PET) backsheet with a Class C fire rating.

 

 

GROUNDING 

・ 

Refer to “Grounding” section.

 

 

BATTERY 

・ 

When  PV  modules  are  used  to  charge  batteries,  the 
battery must be installed in a manner, which will ensure 
the performance of the system and the safety of its users. 

Follow the battery manufacturer

’’’’

s safety guidelines 

concerning installation, operation and maintenance 
recommendations

.  In  general,  the  battery  (or  battery 

bank)  should  be  kept  away  from  people  and  animals. 
Select a battery site that is protected from sunlight, rain, 
snow,  debris,  and  is  well  ventilated.  Most  batteries 
generate  hydrogen  gas  when  charging,  which  can  be 
explosive.  Do  not  light  matches  or  create  sparks  near 
the battery bank. When a battery is installed outdoors, it 
should be placed in an insulated and ventilated battery 
case specifically designed for this purpose. 

 

4. SITE SELECTION 

In  most  applications, 

KDxxxGX-LPU

  series  modules 

should  be  installed  in  a  location  where  they  will  receive 
maximum  sunlight  throughout  the  year.  In  the  Northern 
Hemisphere, the modules should typically face south, and 
in the  Southern Hemisphere, the modules should typically 
face  north.  Modules  facing  30  degrees  away  from  true 
South (or North) will lose approximately 10 to 15 percent of 
their  power  output.  If  the  module  faces  60  degrees  away 
from true South (or North), the power loss will be 20 to 30 
percent.  When  choosing  a  site,  avoid  trees,  buildings  or 
obstructions,  which  could  cast  shadows  on  PV  modules 
especially during the winter season when the arc of the sun 

KD205GX-LPU

KD215GX-LPU 

Reviews: