KY-XTRA B.10.01 comes with pre-programmed application:
Figure 63: KY-XTRA B.10.01 application settings
Available Application Settings:
Invert On/Off:
o
Off: Contact closed if inside area
Example: Switch warning lights
o
On: Open contact if inside area
NO (normally open contact) behaviour
Timeout On/Off
o
Off: Keep last known coil message state
o
On: Toggle contact if no ModBus TCP coil message for Timeout-Time period
Timeout Time:
o
Range from 1 second to 59 minutes 59 seconds
Of course, KY-XTRA B.10.01 must be in the same ethernet network segment as the KY-LOC
1D.01.02 device and ‘Switching device’ ip:port must be properly set at the KY-LOC device. IP
settings of the KY-XTRA B.10.01 can be set via the LOGO! display after ‘stopping’ the
application.
Technical data LOGO! 24 RCE (6ED1052-1HB08-0BA1) - Excerpt:
Parameter
Value / Description
Mounting:
DIN RAIL (35mm) or Wall mount
Dimension (WxHxD):
90 x 71.5 (4TE) x 60 [mm]
Weight:
Approx. 240g
Ambient temperature range (non-condensing) -20 … +55 °C
Power Supply Range:
20.4 .. 26.4 VAC, nominal 24VAC
20.4 .. 28.8 VDC, nominal 24VDC
Power consumption @ 24VDC:
25mA .. 185mA
Digital Outputs:
4 x Relay
Short-circuit protection:
No; external fuse necessary
Relay Rated Voltage:
240VAC/VDC
Surge Current:
30A max.
Max Current (Resistive load):
10A