Kyland Technology (Shanghai) Co., Ltd PTS-DR200 Time Server
- 44 -
Press ‘Save’ button to save the current setting when you change setting.
If select ‘GOOSE-S1’ in GOOSE Channel, the setting screen will be shown as:
[Figure 3-27] GOOSE Subscriber Screen (GOOSE-S1)
Table 26 –GOOSE Subscriber Setting (GOOSE-S1)
Items
Parameters
Description
GOOSE Subscriber
Enable
Disable
Activate GOOSE subscriber feature for ETH1.
Enable: Make GOOSE subscriber start working;
Disable: Make GOOSE subscriber stop working.
MAC
0xXXXX
Set APPID of GOOSE message.
Range is between 0x0000 and 0xFFFF.
Default value is 0x0002.
APPID is a 32 bits data with hex display.
GOOSE GoID
PTSTTR/LLN0$GO$gocb1
Set GCB ID of GOOSE message.
It is a string defined by GOOSE standard.
Default value is PTSTTR/LLN0$GO$gocb1.
Provide IEC61850 ICD file, the current
default value is made by this ICD file.
GOOSE GoCBRef
PTSTTR/LLN0$GO$gocb1
Set GCB reference of GOOSE message.
It is a string defined by GOOSE standard.
Default value is PTSTTR/LLN0$GO$gocb1.
Provide IEC61850 ICD file, the current
default value is made by this ICD file.
GOOSE Dataset
PTSTTR/LLN0$dsGOOSE1
Set GCB dataset of GOOSE message.
It is a string defined by GOOSE standard.