Kyland Technology (Shanghai) Co., Ltd PTS-DR200 Time Server
- 34 -
Items
Parameters
Description
Polarity
-
+: positive polarity DC, high level is 1;
-: negative polarity DC, low level is 1.
Press ‘Save’ button to save the current setting when you change setting.
If select ‘O4’ in Channel Group, the setting screen will be shown as:
[Figure 3-21] Output Setting Screen (O4)
Table 20 – Output Setting (O4)
Items
Parameters
Description
Output
Signal
PPS4
IRIG-B4
PPM
PPH
Set output signal type for O4.
PPS4: Set output signal is PPS;
IRIG-B4: Set output signal is IRIG-B;
PPM: Set output signal is PPM;
PPH: Set output signal is PPH.
The PPS, PPM and PPH are pulse signal. The interval is per
second, per minute and per hour sending one pulse.
Second
Compensation
0s
Set second compensation offset for O4.
Unit is second(s);
Range is between -999999999s and 999999999s.
Default value is 0s.
PPS
Compensation
0ns
Set PPS compensation offset for O4.
Unit is nanosecond(ns);
Range is between -250000000ns and 250000000ns.
Default value is 0ns.
IRIG-B
Time
Format
UTC
TAI
Local
Set reference time for IRIG-B output signal of O4.
UTC: Make output time working at UTC format;
TAI: Make output time working at TAI format.