18.1 Dimension sheets
18.1 Dimension sheets
Fitting dimensions KWB Easyfire S with inclined worm and fabric tank
Solid ceiling F90
No sharp objects above the fabric tank
Min. RL 235
Worm can be extended with
worm conveyor extension
Extractor worm 1 – L1=184.2
Extractor worm 2 – L2=139.2
Incline
< 30°
Outline
Ground plan
** at least 30 on the fill side
* The rear of the boiler must be accessible! (On one side at least 60 cm – on the other side at least 20 cm)
** At least 30 cm must remain free on the fill side of the fabric tank!
The fire door control system (F90 wall) is only necessary in Austria!
Germany: Minimum distance 100 cm between fabric tank and boilers to 50 kW!
Chimney / smoke pipe connection from the floor: 10 - 20 kW at least 70 cm, 25 - 30 kW at least 85 cm, at least 20 cm to the ceiling