13 Suction conveyor
13 Suction conveyor
13
FE “GS” SUCTION CONVEYOR, PELLET WORM
Min. 30
Boiler
Room
Solid ceiling F90
Ceiling opening
;
70 mm
Fire-safety collar
Solid ceiling F90
Solid ceiling F90
Min. RL 200
Ricochet protection mat
Conveyor Worm
Inclined floor
Wooden boards
Min. 100
per “step”
To
tal lift 5
m
without step max. 300
Pellet transport hose
max. length 25 m
Chimney diameter and smoke-pipe
execution in accordance with the
“Technical Data Table“ energy saving
damper
;
15 cm with explosion door
Hose Guide
• Max. total lift 5 m
• Max. total lift without step 3 m
• At the latest after 3 m height difference 1 m route horizontally
• All conveyor hose bend radii at least 30 cm.
13.1
Requirements, pellet storage room
(type GS fan, pellet worm, V-sloping floor)
Comply with the instructions in points 1.3 to 1.3.2 in the introduction!