Description of the Light Tower
2-33
KVAL MLX Operation/Service Manual
Description of the Light Tower
The Light Tower indicates the working status of the system. Highly visible indicator lights are
mounted on top of the Electrical Boxes. A series of colors and flashing codes helps determine the
machine error.
Light Position
Category
Descriptions
Machine Status
OFF (Clear)
: Machine not in operation.
White
: Initializing
1 Flash: Waiting for all systems to initialize
Red: Machine Error
Solid: General Error
•
1 Flash: EtherCat Device not Ready to Run
•
2 Flashes: VFD, Servo, or Motor Error
•
3 Flashes: 24 VDC Power Error
Yellow: External Error
Solid: General Error
•
1 Flash: 3 Phase Voltage Error
•
2 Flashes: Low Air Error
Blue:
Operator Status
Solid: Waiting for Operator
•
1 Flash: Reposition Door
Green: Machine is Operational
Safety
OFF (Clear):
Safety Project not Running
Red:
Safety PLC Error
Blue:
Waiting for Safety Re-Set
•
Solid: General Error
•
Flashing: Not Ready to Re-Start (E-Sop Switch is Active)
Green:
Machine is Operational
Control Power
Off:
No Control Power
ON (Green):
24 VDC Control Power ON
2
1
3
Ready to Work
Light Tower Rev 2
Summary of Contents for MLX
Page 59: ...About the Tool Config Tabs 2 29 KVAL MLX Operation Service Manual ...
Page 64: ...Description of the Light Tower KVAL MLX Operation Service Manual 2 34 ...
Page 90: ...System IT Administration KVAL MLX Operation Service Manual 4 4 ...
Page 117: ...Collet Torque Values 5 27 KVAL MLX Operation Service Manual ...
Page 118: ...Collet Torque Values KVAL MLX Operation Service Manual 5 28 ...
Page 141: ......
Page 142: ......
Page 143: ......