Kurz
B
‐
Series
Operations
Guide
4–24
Program Mode
Advanced Setup
Option 10 — Setting Up the NE-43 Alarm
The
flow
meter
supports
the
NAMUR
specification
NE
‐
43
alarm
on
the
4
‐
20
mA
signal.
The
range
for
the
non
‐
alarmed
analog
output
signal
is
between
3.8
and
20.5
mA.
Figure 4
‐
1.
4
‐
20
mA
operation
with
the
NE
‐
43
alarm
The
following
flow
meter
error
events
cause
a
NE
‐
43
alarm:
•
External
analog
input
out
of
range
•
Sensor
type
does
not
match
board
build
•
Unable
to
write
configuration
file
to
EEPROM
•
Abnormal
sensor
node
voltages
•
Sensor
type
does
not
match
configuration
•
Sensor
over
‐
voltage
crowbar
engaged
•
Sensor
control
drive
stopped
responding
•
ADC
failed
to
convert
measurement
•
High
sensor
or
wire
leakage
•
Rps
sensor
lead
open
circuit
•
Wire
loop
resistance
above
high
limit
•
Rtc
resistance
below
low
limit
and
above
high
limit
•
Rp
resistance
below
low
limit
and
above
high
limit
•
Flow
rate
above
design
limit
To
access
the
NE
‐
43
Alarm
Setup
menu
in
Program
mode:
1>
Press
P
.
2>
Enter
the
Advanced
access
code,
and
then
press
E
.
3>
Press
2
to
invoke
the
Quick
Jump
option.
4>
Press
10
for
the
NE
‐
43
Alarm
Setup
menu,
and
then
press
E
.
NE-43 ALARM TYPE
>HIGH OUTPUT ^v
The
NE
‐
43
alarm
type
prompt
appears.
—
A
LOW
OUTPUT
drives
the
4
‐
20
mA
output
to
≤
3.6
mA
when
a
meter
fault
occurs.
—
A
HIGH
OUTPUT
drives
the
4
‐
20
mA
output
to
≥
21
mA
when
a
meter
fault
occurs.
NE-43 Alarm
(low value kick-out)
NE-43 Alarm
(high value kick-out)
Saturate
Saturate
Normal Operation
3.6 3.8
20.5 21
0
mA
Summary of Contents for 410FTB
Page 1: ...Operations Guide for B Series Flow Meters 368042E...
Page 4: ...Kurz B Series Operations Guide iv...
Page 9: ...Kurz B Series Operations Guide ix Preface...
Page 33: ...Kurz B Series Operations Guide 1 20 B Series Flow Meter Modes Menus...
Page 65: ...Kurz B Series Operations Guide 2 32 B Series Flow Meter Display Mode Options...
Page 141: ...Kurz B Series Operations Guide 4 68 Program Mode Advanced Setup...