CO2 CONTROL - assembly and operating instructions
-8-
2
Assembly
2.1
General notes in accordance with BGR 228
The gas detection system installer is responsible and therefore liable for the correct
installation and handover of the equipment.
Gas detection devices (equipment requiring special monitoring) may only be planned,
installed and maintained by specialist personnel.
To ensure safe operation, only ancillary components approved by KUNDOxT may be
connected to the CO2 CONTROL safety system.
BGR 228 /DIN 6653-2 stipulates all of the statutory measures and the state of the art for the installation and operation of gas detection equipment in dispensing
systems.
DIN EN 378 refers to the state of the art for the application, operation and functional checking of gas detection devices in the refrigeration field.
The rules therein must normally be observed and complied with. All further measures for the installation/assembly of the CO2 CONTROL gas detection system
are given in the sections below.
Note: Please observe the separate assembly instructions for
CO2 CONTROL AM
!
2.2
System design
The overview identifies the possible system component connections via the
distributor
. The PA version has a second control line (5-wire) to the building
control/control system.
The sensor unit may only be operated in an upright, assembled condition (see Fig.).
The CO2 CONTROL version is supplied with power through the control line from the building control/control system. An input for power supply and control is
available for additional alarm units.
CO2 CONTROL AM / AM PLUS basic package
CO2 CONTROL PA basic package
Expansion with a second sensor unit
Signal unit
to secure further
entrances/doors
Expansion with a second sensor unit
Signal unit
to secure further
entrances/doors
-
control line 3m
-
control line variabel
Sensor unit 1
Sensor unit 2
Distributor
Switching unit
Distributor
Distributor
Warning unit
potential free
outputs
(PA, MA, Fault and Operation)
-
control line 3m
-
control line variabel
Switching unit
Sensor unit 1
Sensor unit 2
Distributor
Distributor
Distributor
Supply 230V, control outputs
(PA, MA, Sum, Fault and Operation)
Connection
for an
external
Alarm unit
AM /
AM Plus