Gateway PROFINET IRT Slave
23
– Profile specific type
– I&M Version
I&M 1 Data
I&M 1 Data is stored permanently in the gateway component. They can be read and written by
the PROFINET controller via Record Read with Api 0, Slot 0, Subslot 1, Index 0xaff1.
I&M 2 Data
I&M 2 Data is stored permanently in the gateway component. They can be read and written by
the PROFINET controller via Record Read with Api 0, Slot 0, Subslot 1, Index 0xaff2.
I&M 3 Data
I&M 3 Data is stored permanently in the gateway component. They can be read and written by
the PROFINET controller via Record Read with Api 0, Slot 0, Subslot 1, Index 0xaff3.
I&M 4 Data
I&M 4 Data is stored permanently in the gateway component. They can be read and written by
the PROFINET controller via Record Read with Api 0, Slot 0, Subslot 1, Index 0xaff4.
5.4.2 Diagnosis Alarm
If communication to the partner gateway component is interrupted, the gateway component for
PROFNET sends a diagnosis alarm to the controller:
– The alarm is sent out from API 0, Slot 0, Subslot 1
– The alarm is sent as channel diagnosis with channel 0x8000
– The alarm has the priority "Maintenance Required”
– Error type is 0x0100 (first user defined error)
a) Check whether the plug-in jumper is connected correctly to both gateway components.
b) Check whether the partner gateway component is connected to the power supply.
As soon as the communication between the two gateway components is working, the gateway
component for PROFINET sends a diagnostic telegram to the PROFINET controller.
More detailed information on the topic of diagnosis alarm can be found in the specifications for
PROFINET.
Configuration
Summary of Contents for PROFINET IRT Slave
Page 1: ...User Manual Gateway PROFINET IRT Slave DO0413R00 3 31 2022...
Page 31: ...Gateway PROFINET IRT Slave 31 k Click on Set The IP address is now set Integrated Servers...
Page 38: ...KUNBUS GmbH 38 Gateway PROFINET IRT Slave...
Page 39: ...KUNBUS GmbH Gateway PROFINET IRT Slave 39...
Page 40: ......