Status information of the driver
The “State of status machine of driver” can be read in the diagnostic monitor.
IP address of config-
uration tool (1)
IP address of a connected configuration tool (1)
IP address of config-
uration tool (2)
IP address of a connected configuration tool (2)
“Name” column
Description
Designation
Value
Description
INST_NOT_AVAILABLE
0x0001
Initial state if the instance has not yet been ini-
tialized.
INST_RUNNING
0x0002
This status bit indicates that the Interbus was
started successfully and that I/O data
exchange can take place.
INST_STOP_USER
0x0004
This status bit is set if the Interbus has been
stopped by the driver or by a user action.
INST_STOP_ERR
0x0008
This status bit is set if an error has occurred in
the Interbus master ring, preventing an update
of all I/Os, e.g. in the case of a bus error.
INST_CLEAR_MPM_OUT
0x0010
This status bit is set if the outputs are set to 0 in
the event of an error.
INST_WAITING_FOR_EX_STA
RT
0x0020
This status bit is set if the Interbus is to be
started by means of a boot project or “exter-
nally” and is waiting for this start.
INST_STOP_WARN
0x0040
This status bit is set if the driver is to signal an
error in the case of a periphery fault when writ-
ing and reading I/Os.
INST_RUN_WATCHDOG_STA
RT
0x0080
This status bit is set if the Interbus has already
been started, but the watchdog is still to be trig-
gered. The watchdog is not triggered until the
cyclical read and write function is executed.
The start of the watchdog must be delayed until
the cyclical read and write function has been
activated.
INST_STOP_FREEZE
0x0100
This state is set once the driver has been set to
the Freeze state.
INST_STOP_RESET
0x0200
This status bit is set if the driver attempts to
restart the Interbus.
INST_STOP_WATCHDOG
0x0400
This status bit is set if the watchdog has
expired.
INST_STOP_HW_ERR
0x0800
This status bit is set if a hardware error has
been detected or signaled by the firmware.
INST_STOP_SLV_ERR
0x1000
This status bit is set if the driver is no longer to
update I/O data once the slave ring has sig-
naled an error.
INST_ERR_DETECTING
0x2000
This status bit indicates that the firmware has
started searching for an error in the Interbus
master ring.
Summary of Contents for Interbus 1.1
Page 8: ...8 65 Issued 29 11 2012 Version KR C4 Interbus 1 1 V2 en PDF Interbus 1 1...
Page 12: ...12 65 Issued 29 11 2012 Version KR C4 Interbus 1 1 V2 en PDF Interbus 1 1...
Page 20: ...20 65 Issued 29 11 2012 Version KR C4 Interbus 1 1 V2 en PDF Interbus 1 1...
Page 62: ...62 65 Issued 29 11 2012 Version KR C4 Interbus 1 1 V2 en PDF Interbus 1 1...
Page 64: ...64 65 Issued 29 11 2012 Version KR C4 Interbus 1 1 V2 en PDF Interbus 1 1...
Page 65: ...65 65 Issued 29 11 2012 Version KR C4 Interbus 1 1 V2 en PDF Interbus 1 1...