22 / 65
Issued: 29.11.2012 Version: KR C4 Interbus 1.1 V2 en (PDF)
to any value between 1 and 8. The default value is 1. It is not necessary to
change the card number if only one Interbus card is used.
4 ... 6: Additions
DIP switches 4 to 6 are reserved for expansions and must not be changed.
7: Baud rate
DIP switch 7 is used to set the baud rate. The DIP switch is set to OFF by de-
fault, i.e. the baud rate is detected automatically. This setting must not be
changed.
8: Test mode
DIP switch 8 is used to activate the test mode. If the system is rebooted with
test mode active, the controller board starts up the Interbus with physical ad-
dressing and activates it. During test mode, the controller board does not re-
spond to instructions from the host system (PC). The controller board
initializes the Interbus system and then starts it up automatically. Outputs are
not set.
6.3
DIP switches on the slave module
The DIP switches are on the top left-hand side of the slave module.
KUKA default
: DIP 1 … 4 OFF, DIP 5 ON, DIP 6 … 9 OFF, DIP 10 ON
The card number must be specified when the driver is installed. It is
advisable to make a note of it after making the setting.
Card number
DIP switch 1
DIP switch 2
DIP switch 3
1 (default)
OFF
OFF
OFF
2
ON
OFF
OFF
3
OFF
ON
OFF
4
ON
ON
OFF
5
OFF
OFF
ON
6
ON
OFF
ON
7
OFF
ON
ON
8
ON
ON
ON
In normal operation of the controller board, test mode must be deac-
tivated by setting switch 8 to OFF.
Summary of Contents for Interbus 1.1
Page 8: ...8 65 Issued 29 11 2012 Version KR C4 Interbus 1 1 V2 en PDF Interbus 1 1...
Page 12: ...12 65 Issued 29 11 2012 Version KR C4 Interbus 1 1 V2 en PDF Interbus 1 1...
Page 20: ...20 65 Issued 29 11 2012 Version KR C4 Interbus 1 1 V2 en PDF Interbus 1 1...
Page 62: ...62 65 Issued 29 11 2012 Version KR C4 Interbus 1 1 V2 en PDF Interbus 1 1...
Page 64: ...64 65 Issued 29 11 2012 Version KR C4 Interbus 1 1 V2 en PDF Interbus 1 1...
Page 65: ...65 65 Issued 29 11 2012 Version KR C4 Interbus 1 1 V2 en PDF Interbus 1 1...