In addition to the remote start or start in the event of a mains failure, the genset can also be started 
via the Sprinkler command (see further in this document). 

8.4. 

Mains circuit breaker tripping 

The automatic system can be parameterised in such a way that the start and the switching to gen-
erator  operation  can  also  be  carried  out  if  the  mains  switch  fails  due  to  an  error.  (for  systems  per 
VDE  107).  In  this  case,  the  genset  starts  automatically  and  takes  over  as substitute  power  supply. 
The internal mains switch monitoring must be parameterised to a fault message for the activation of 
this function. The green M

AINS IS 

O

N

 LED flashes for the display of this error. 

For switching back to the mains, the  M

AINS CIRCUIT BREAKER TRIPPING

 message must be cleared. In 

the event of problem-free mains voltage, the automatic system switches back to mains operation af-
ter expiry of the switching-back time. 

8.5. 

Test operating mode 

After button selection to the T

EST 

position, the start program is triggered. The 

START CONTROL

 indica-

tion  flashes  as  long  as  there  is  no  start  release  and  the 

SWITCH  ON  AUXILIARY  DRIVES

  signal  is  pre-

sent. If no auxiliary drives are required (for start release), terminal 8 from X2, 

START RELEASE

 should 

be switched with L-.  

If the generator voltage lies within the parameterised value limits with its voltage and frequency val-
ues,  the  mains  can  be  switched  off  and  the  generator  can  be  switched  on  with  the  G

EN

-O

N

 (

I

)  or 

M

AINS 

O

FF

 (

O

) button, or the generator can be switched off and the mains can be switched o n with 

M

AINS 

O

N

 (

I

) or G

EN

-O

FF

 (

O

) button. 

If a mains failure occurs or the 

MAINS BREAKER TRIPS

 (if parameterised) during test operation, or if a 

remote start command occurs, operation switches over to generator operation. Then, it is not possi-
ble to manually switch off the generator circuit breaker. Manual operation of the switch is only pos-
sible  after  mains  power  returns  (possibly  also  clearing  the  M

AINS  CIRCUIT  BREAKER  TRIPPING

  alarm) 

and after the switching-back time has elapsed. 

In order to switch off the genset, the O

FF 

or (if the remote start command is not present)  A

UTOMATIC 

operating mode must be selected. 

8.6. 

Sprinkler operation 

The following functions are intended for the operation of an electrical sprinkler pump:  

switching of all switching-off alarms (overspeed alarm remains switched off for electronic speed
sensor, demand VDS 2100-22) to warning,

optionally, the inhibition of the generator switch-off function for 

GENERATOR OVERCURRENT

, for ex-

ample,

start program to 6 (parameterisable) start attempts,

upon sprinkler request being withdrawn: Cessation of the sprinkler operation after the 

SPRINKLER

RUN

-

ON TIME

, or only manual switching off,

for the duration of the acceleration time of the sprinkler pump: Switching off the emergency pow-
er consumers or no interruption of the emergency power supply.

The supply of the sprinkler pumps is usually taken care of directly by the generator and thus prior to 
the switch to the emergency power consumers. If a sprinkler request is arises, the genset starts. In 
the event of the emergency power failure, the consumers can be switched off for a parameterisable 
period of time in order for enough 
energy to be available for the acceleration time of the pump. Furthermore, it is possible to parame-
terise that the consumer switches remain switched on or switched off in the event of an overload on 
the side of the consumers. 

Sprinkler operation is automatically cancelled after the sprinkler requirement is removed after a stip-
ulated run-on time or can only be ended manually (demand VDS 2100-22).

 

If the automatic system 

is parameterised for manual shutdown, the LED of the O

FF 

operating mode flashes as soon as the 

sprinkler input is free. Stopping can then be carried out via the O

FF 

operating mode (or always via 

Emergency Stop). 

Summary of Contents for KEA 291 NSTR

Page 1: ...parameterisable alarm and operating indicators which can be labelled by easily replaceable paper strips as well as four general displays are displayed through LEDs The pa rameterisation can be perform...

Page 2: ...e 6 8 4 Mains circuit breaker tripping 7 8 5 Test operating mode 7 8 6 Sprinkler operation 7 9 Error messages Programmable operation indicators 8 9 1 Use as an operational indicator 8 9 2 Use as an er...

Page 3: ...his also applies for all relays and inductances that are used differently in the switchgear or are externally controlled 5 General description The KEA 291 NSTR automatic system is a further developmen...

Page 4: ...ng mode is prevented The operating modes described below can be selected using the keys 6 1 Start key The motor can be started in MANUAL operating mode by actuating this button If the motor needs to b...

Page 5: ...ion speed during start up recognised through the D signal of the generator through the speed sensor signal or through the generator voltage in accordance with the parameterisation Switching on the sta...

Page 6: ...art command does not lead to automatic switch on of the generator Also the mains is not automatical ly switched on if an error message occurs during generator operation e g GENERATOR OVERCURRENT which...

Page 7: ...mote start command occurs operation switches over to generator operation Then it is not possi ble to manually switch off the generator circuit breaker Manual operation of the switch is only pos sible...

Page 8: ...m is locked The parameterisation is described in the service instructions 9 3 Alarms 9 and 10 Both these alarms can be delayed from 0 to 240 sec by the signal transmission i e for the alarm contact to...

Page 9: ...tch on duration of the stop solenoid the stop process is repeated and the FAILED START MOTOR ERROR message is displayed The automatic system is not locked so that the genset can immediately switch to...

Page 10: ...sec Idle time 180 sec Sprinkler operation run on time 600 sec Stop time 30 sec 13 2 Start process gas engine Starter on If the starter speed is exceeded the switching on of the ignition is delayed e...

Page 11: ...UNDERVOLTAGE display is actuated in the event of a disrupted rotating field Adjustable switching points 50 300 Volt Mains frequency 45 to 65 Hz adjustable in 0 01 Hz steps from 40 to 70 Hz 2 phase gen...

Page 12: ...STR_EN_Ver 2015 03 20_EN doc 12 14 12 Alfred Kuhse GmbH Telephone 49 4171 798 0 E mail kuhse kuhse de Subject to technical changes An der Kleinbahn 39 21423 Winsen Fax 49 0 4171 798 117 http www kuhse...

Page 13: ...20_EN doc 13 14 ______________________________________________________________________________________ Alfred Kuhse GmbH Telefon 49 4171 798 0 kuhse kuhse de Subject to technical changes An der Klein...

Page 14: ...hse GmbH Telefon 49 4171 798 0 kuhse kuhse de Technische nderungen vorbehalten An der Kleinbahn 39 D 21423 Winsen Luhe Telefax 49 4171 798 117 www kuhse de 14 14 Operating instructions for KEA 252 PA...

Reviews: