4.5.2.3 LED "Power"
The LED labeled "Power" indicates the state of the I/O module's I/O power supply.
The module is not monitored for low voltage states.
4.5.2.4 LEDs "Channel"
State
LED
Explanation
On
Green, on
Input signal TRUE / output enabled
Off
Off
Input signal FALSE / output disabled
4.5.3 Function
The DI16/DO16 module features 16 digital inputs and 16 digital outputs.
4.5.3.1 Variable
Variable
Data type
Explanation
DigitalInputn
BOOL
Digital input (n=0...15)
DigitalOutputn
BOOL
Digital output (n=0...7)
reserved
BOOL
Unused output addresses
4.5.4 Technical data
Digital inputs .................................................. 16
Input delay ..................................................... 1ms (typically)
Signal level .................................................... Off:
-3 … 5V
(EN 61131-3, Typ1)
On:
15V … 30V
Digital Outputs ............................................... 8
Max. current ................................................... 1.0A per output
Total current .................................................. max. 8A
Connector IO/Power ...................................... Plug 36-pole
Controller ....................................................... ASIC ET1200
Baud rate ....................................................... 100 Mbit/s
Connector E-Bus ........................................... 10-pin system plug in side wall
End module ................................................... not required
Power supply ................................................. 24V DC -20% +25%
E-bus load...................................................... 135mA
Part no ........................................................... 694.450.02
Approvals: ......................................................