Kendrion Kuhnke Automation GmbH
AI8-I
120
11/25/2016
4.20.5 Technical data
Analog Inputs ................................................. 8
Measuring range ............................................ 0 …20mA, 4…20mA (End value 20mA)
Resolution ...................................................... 12 Bit
Start AD-conversion ...................................... DC-synchronous, SM-synchronous
Conversion time ............................................. 290µs (if all channels are active)
Internal resistance ......................................... < 300
Ω
Limit frequency Input filter ............................. < 100kHz
Measuring error ............................................. < ±0,5%, typically < ±0,4% of the end value
Baud rate ....................................................... 100 Mbit/s
Controller ....................................................... ASIC ET1200
Connector E-Bus ........................................... 10-pin system plug in side wall
End module ................................................... not required
Connector IO/Power ...................................... Plug 36-pole
Power supply ................................................. 24V DC -20% +25%
E-bus load...................................................... 190mA
Part no ........................................................... 694.441.04 (planned)
Part no ........................................................... 694.441.54 (CoE)
Approvals: ......................................................