GENERAL
GL6000A-AU-B, GL6000D-AU-B,GL9000A-AU-B, GL9000D-AU-B, WSM
G-13
6. MAINTENANCE CHECK LIST
Observe the following for service and maintenance.
The lubricating oil change intervals listed in the table below are for classes CG, CE and CD lubricating oil of API
classification with a low-sulfur fuel in use. If the CF-4 of CG-4 lubricating oil is used with a high-sulfur fuel, change the
lubricating oil at shorter intervals than recommended in the table below depending on the operating condition.
CAUTION
• When checking and servicing the generator, be sure to level and stop the engine.
9Y1211607GEG0021US0
9Y1211607GEG0022US0
No.
Item
Indication on hour meter
Refer-
ence
page
Daily
Initial
50 hours
Every
50 hours
Every
100
hours
Every
200
hours
Every
300
hours
Every
400
hours
Every
500
hours
1 Check of engine oil level
2 Check of coolant level
3
Check of residual current circuit breaker
(RCBO)
4 Change of engine oil
5 Check of battery electrolyte level
6 Replacement of oil filter cartridge
7 Check of fuel hoses and clamp bands
8 Cleaning of air cleaner primary element
9 Check of fan belt tension
10 Cleaning of fuel filter element
11 Check of radiator hoses and clamp bands
12 Check of intake air hose
13 Check of generator's brush ware
14 Check of generator's slip-ring
15 Replacement of fuel filter element
16 Cleaning of water jacket and radiator interior
No.
Item
Indication on hour meter
Refer-
ence
page
Every
800 hours
Every
1000 hours
Every
1500 hours
Every
3000 hours
Every
1 year
Every
2 years
1 Replacement of fan belt
2 Check of valve clearance
3 Check of generator's ball bearing
4 Check of fuel injection pressure
5 Check of nozzle spraying condition
6 Check of nozzle valve seat tightness
7 Check of injection pump
8 Replacement of air cleaner primary element
9
Check of damage in electric wiring and loose
connections
10 Replacement of fuel hoses and clamp bands
11
Replacement of radiator hoses and clamp
bands
12 Replacement of battery
13 Change of radiator coolant (L.L.C.)
KiSC issued 06, 2016 A