12.9
Frequency < 0 Hz
(Switch Mode = 8)
With parameter setting “Switch Mode” = 8, the direction of the frequency is monitored.
The function is always active. With negative frequencies (f < 0 Hz), the output is set to
ON. The output will reset with positive frequencies (f > 0 Hz) or with standstill (f = 0 Hz)
after expiration of the Standstill Time.
Relevant Parameters
Remark
„Switch Mode
“
= 8
„Pulse Time
“
statically = 0 or pulse duration in x seconds
„Standstill Time“
standstill time in seconds
„Output Mode“
homogenous or inverse (affects the Safety Integrity Level SIL/PL)
Relevant input functions
Remark
none
none
Example:
The transition from a positive to a negative frequency will cause an immediate change of
the output state. Only in case of a transition from a negative frequency to zero, the
output will not change before Standstill Time has elapsed.