R60047.0002 - Index 2
EN – page 70 / 115
12.7
Frequency Band (Switch Mode = 6)
With parameter setting “Switch Mode” = 6, the frequency is monitored within a frequency
band.
The function is always active. The switching positions inside the frequency band are at
/- Hysteresis. Only positive Presel values are allowed.
Relevant Parameters
Remark
„Switch Mode
“
= 6
„Pulse Time
“
statically = 0 or pulse duration in x seconds
„Hysteresis
“
+/-range from the center point (Presel. Value)
„Startup Mode“
type of start-up delay
„Startup Output“
output assignment for start-up delay
„Lock Output“
lock function
„Output Mode“
homogenous or inverse output configuration (affects the Safety Integrity
Level SIL/PL)
„Presel.
.
“
center
„Delay
“
„Input Mode “
configuration of the control inputs (affects the safety level SIL/PL)
„ IN Function“
function of the control input
„ IN Config“
switching behaviour (single-channel, two-channel, inverse, homogeneous,
dynamic, static)
„GPI Err Time“
Max. permissible delay time during illegal conditions
Relevant input functions
Remark
Clear lock function, e.g. parameter „IN1 Function“ = 1 … 6
When lock function is active only
Switchover switching points, e.g. parameter „IN2 Function“ = 13
Only when switchover is active
Example:
With Presel = 1000.0 Hz and Hysteresis = 10 %, frequencies f < 900 Hz are declared as underspeed
and frequencies f > 1100 Hz as overspeed.
Summary of Contents for SMC1.3
Page 44: ...R60047 0001 Index 2 DE Seite 44 120 8 2 Montage Demontage...
Page 49: ...R60047 0001 Index 2 DE Seite 49 120...
Page 117: ...R60047 0001 Index 2 DE Seite 117 120 20 Zertifikat...
Page 118: ...R60047 0001 Index 2 DE Seite 118 120...
Page 119: ...R60047 0001 Index 2 DE Seite 119 120...
Page 163: ...R60047 0002 Index 2 EN page 43 115 8 2 Mounting Dismounting...
Page 168: ...R60047 0002 Index 2 EN page 48 115...
Page 234: ...R60047 0002 Index 2 EN page 114 115 20 Certificate...