R60047.0002 - Index 2
EN – page 67 / 115
12.4
Standstill (Switch Mode = 3)
With parameter setting “Switch Mode” = 3, the frequency is monitored for standstill. The
function is always active. The output is set after detection of frequency 0 Hz and
expiration of the standstill time. When a frequency different from zero is detected, the
output will be reset. Parameter “Wait Time” determines the threshold under which a
frequency is taken as zero.
Relevant Parameters
Remark
„Switch Mode
“
= 3
„Pulse Time
“
statically = 0 or pulse duration in x seconds
„Standstill Time“
standstill time in x seconds
„Output Mode“
homogenous or inverse output configuration (affects the Safety Integrity
Level SIL/PL)
Relevant input functions
Remark
none
none
Example:
With a Wait Time setting of 0.01 seconds, all frequencies < 100 Hz will be taken as zero (f
= 0).
The expiration of Standstill Time starts as soon both channels report 0 Hz. When this
time has expired and both frequencies are still 0 Hz, the standstill output will be set. As
soon one of the two frequencies becomes different from zero again, the standstill
output will be reset.
Summary of Contents for SMC1.3
Page 44: ...R60047 0001 Index 2 DE Seite 44 120 8 2 Montage Demontage...
Page 49: ...R60047 0001 Index 2 DE Seite 49 120...
Page 117: ...R60047 0001 Index 2 DE Seite 117 120 20 Zertifikat...
Page 118: ...R60047 0001 Index 2 DE Seite 118 120...
Page 119: ...R60047 0001 Index 2 DE Seite 119 120...
Page 163: ...R60047 0002 Index 2 EN page 43 115 8 2 Mounting Dismounting...
Page 168: ...R60047 0002 Index 2 EN page 48 115...
Page 234: ...R60047 0002 Index 2 EN page 114 115 20 Certificate...